SECTION 7 – OPERATING AUXILIARY EQUIPMENT
NOTE

7-1. Standard Receptacles

1
4
OM-945 Page 20
If the unit is extremely overloaded, weld and generator power will stop. Turn unit off
and restart to reset the generator protection circuit and restore weld and generator
power output.
If the rated output of the unit is exceeded, engine speed may vary rapidly until the
weld or generator power load is reduced.
The welding generator provides power while welding and with the Amperage
control in any position. However, under these conditions equipment connected to
the welding generator may be subject to larger than normal voltage fluctuations. It
is recommended that only lamps be powered under these conditions.
Y If unit does not have GFCI re-
1
RC1 supplies 60 Hz single-phase
power at weld/power speed. Maxi-
mum output is 10 kVA/kW.
5
2
6
3
2
3
RC2 and RC3 supply 60 Hz single-
phase power at weld/power speed.
Maximum output from RC2 or RC3
is 2.4 kVA/kW.
4
CB1 protects the ac receptacles
from overload. If CB1 opens, the ac
receptacles do not work.
.
5
6
CB2 protects RC2 and CB3 pro-
tects RC3 from overload. If a circuit
breaker opens, the receptacle does
not work.
.
Combined output of all receptacles
limited to 10 kVA/kW rating of the
generator.
EXAMPLE: If 20 A is drawn from
each 120 V duplex receptacle, only
21 A is available at the 240V
receptacle:
2 x (120 V x 20 A) + (240 V x 21 A)
= 10 kVA/kW (approx.).
ceptacles,
use
GFCI-
protected extension cord.
120/240 V 50 A AC Recep-
tacle RC1
120 V 20 A AC Duplex Recep-
tacle RC2
120 V 20 A AC Duplex Recep-
tacle RC3
Circuit Breaker CB1
Move CB1 toggle switch to On
position to reset circuit break-
er. If breaker continues to open,
contact Factory Authorized
Service Agent.
Circuit Breaker CB2
Circuit Breaker CB3
Press button to reset circuit
breaker. If breaker continues to
open,
contact
Factory
Authorized Service Agent.
202 069-A