Viessmann VITODENS 200-W Technical Manual page 12

Gas condensing boiler 17.0 to 105.0 kw as a multi-boiler system up to 420.0 kw
Table of Contents

Advertisement

Vitodens 200-W
Residual head of the circulation pump
120
1200
1
110
1100
100
1000
90
900
80
800
70
700
60
600
50
500
40
400
30
300
20
200
10
100
0
0
0
Flow rate in l/h
A Stage 1
B Stage 2
C Stage 3
Note
Observe further details regarding the use of a low loss header (see
page 35).
If the residual head of the circulation pumps (available as accessories)
is insufficient to overcome the following system pressure drop values,
install an additional, external circulation pump on site.
In such cases, use a low loss header.
Pressure drop (primary circuit)
For sizing a circulation pump on site (when connecting to DHW cylinder
from connection set)
60
600
50
500
400
40
30
300
20
200
10
100
0
0
0
1000
Flow rate in l/h
VIESMANN
12
(cont.)
1000
2000
2000
3000
4000
A
3000
4000
5000
6000
7000
C
B
5000
5000
6000
VITODENS 200-W