4.10 CORROSION PROTECTION

Periodically wash and wax the enclosure using auto-
motive type products. Frequent washing is recom-
mended in salt water/coastal areas. Spray engine
linkages with a light oil such as WD-40.

4.11 OUT OF SERVICE PROCEDURE

4.11.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and will be out of service longer than 90 days, pre-
pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, switch to the OFF
position.
4. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
5. Set the AUTO/OFF/MANUAL switch to OFF and
turn off the utility power to the transfer switch.
Remove the 7.5A fuse from the generator control
panel. Disconnect the battery cables as outlined
in "General Hazards".
6. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
oil. See "Engine Oil Recommendations".
7. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging
agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed
as follows:
1. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF .
2. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommend-
ed oil is used in the engine (see the Engine Oil
Recommendations section). If necessary, drain
and refill with the proper oil.
3. Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with dis-
tilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery.
See "Specifications," for type and size.
Section 4 — Maintenance
Air-cooled Generators
4. Clean and wipe the entire generator.
5. Make sure the 7.5A fuse is removed from the
generator control panel. Reconnect the battery.
Observe battery polarity. Damage may occur if the
battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 7.5A fuse into the generator control
panel. Start the unit by moving the AUTO/OFF/
MANUAL switch to MANUAL. Allow the unit to
warm up thoroughly.
8. Stop the unit by setting the AUTO/OFF/MANUAL
switch to OFF .
9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
If the battery was dead or disconnected, the exer-
cise timer (single cylinder), current date and time
(v-twin) must be reset.
4.11.3 ACCESSORIES
There are performance enhancing accessories avail-
able for the air-cooled generators.
Cold Weather Kits
where temperatures regularly fall below 10° F (-12°
C).
Scheduled Maintenance Kits
necessary to perform maintenance on the genera-
tor along with oil recommendations.
Auxiliary Transfer Switch Lockout
of the transfer switches to completely lock out
one large electrical load by tying into its control
system.
A Fascia Skirt Wrap
units. It's available for all other current produc-
tion air-cooled units. It snaps together to provide a
smoothing, contoured look as well as rodent/insect
protection.
The PowerMaster
load prioritization device allows
home owners to potentially operator two (2) large
electrical loads by giving one (1) priority over the
other.
The Remote Monitor System
mounted, box that indicates generator run status
and allows for exercise programing as well as pro-
vide maintenance reminders.
Touch-up Paint Kits
tain the look and integrity of the generator enclo-
sure. These kits include touch-up paint and
instructions if the need should arise.
For more details on accessories, please contact an
Authorized Dealer.
NOTE:
are recommended in areas
include all pieces
enables any
is standard on all 20kW
is a wireless, indoor
are very important to main-
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8kw10kw12kw14kw16kw17kw ... Show all

Table of Contents