ERROR CODES

AFTER ENSURING THAT ALL ACTIONS HAVE BEEN CARRIED OUT RESET THE BOILER (REFER TO SECTION 5.4) IF ANY Y OF
THE BELOW FAULTS OCCUR DURING INSTALLATION PLEASE REFER TO THE ACTIONS, HOWEVER IF ANY OTHER ER R ROR
RESET LOCK-OUT CODES
ERROR CODE
DESCRIPTION
1
Overheated
appliance
2
Different check faulty / Sensor temperature
Flame for 15 seconds
3
No gas or Lockout flame Low gas pressure.
signal / No flame,
Lockout after 5 ignition operation
attempts
4
Flue gas sensor /
No flame
BLOCKING CODES
ERROR CODE
DESCRIPTION
5
Defective sensor or
thermal fuse blown
6
Defective gas valve /
Flame continues after
demand ends
7
Defective fan / No flame Missing or Erroneous RPM
A
PCB error / No flame
b
Activate BCC / No flame New BCC
C
Safety system failure / Failure of internal self
No flame
E
BCC error / No flame
h
No flame
0
Different check faulty / Water flow rate too low
Flame for 15 seconds
P
Error in power supply / Low mains voltage
No flame
No light indication
6
CODE IS SHOWING PLEASE CONTACT THE INSTALLER OR TECHNICAL HELP LINE E : : 01926 834834
REASON
ACTION
CH Water temperature
•Check no air is in heat exchanger / CH system
greater than 105°C
•Check external pump operation
•Check PCB / X1C connector
•Check flow thermistor
•Check wires to sensors not crossed
• Check water pressure
differential incorrect
• Check external pump / CH system blockage
• Check no air is in heat exchanger / CH system
• Check flow, and return sensors
• Check gas supply
Loss of flame signal during
• Check gas service cock
• Check gas valve and lead
• Check detection electrode / lead
• Check PCB / X2A & X2B connectors
• Check spark generator /spark electrode
• Check mains earth lead continuity
Flue gas temperature greater
• Check flue sensor
than 95°C
• Check flue system
• Check no air is in heat exchanger / CH system
• Check external pump
• Check PCB / PCB connectors
REASON
ACTION
Defective flow, return or flue • Check wiring to sensors
sensor or heat exchanger
• Check PCB / X6 & X8 connectors
reached maximum safe
• Check flow, return and flue sensors
working temperature
• CHECK THERMAL FUSE IS OPEN CIRCUIT.
IF SO REPLACE HEAT EXCHANGER (SEE 10.8)
5 sec flame signal after burner • Check gas valve and lead
is switched off
• Check PCB
• Check fan
signal
• Check mains fan lead & connector
• Check low voltage fan lead & connector
• Check PCB / X3 connector
Internal error
• Check PCB
• Turn CH control knob to reset twice to activate
• Check PCB
checking system
• Check BCC is initialised
Incorrect / missing BCC
• Reset or replace BCC
Faulty connector
• Check PCB / X1A connector
• Check water pressure
• Check external pump / CH system blockage
• Check no air is in heat exchanger / CH system
• Check wires to sensors not crossed
• Check flow, and return sensors
• Check mains voltage
• Check PCB connectors
Defective power supply
• Check power supply
• Check PCB / X1B connector
• Check PCB fuse
RESET POSSIBLE
Yes
Auto Restart When Fixed
Yes
Yes
RESET POSSIBLE
Auto Restart When Fixed
© Dimplex Boilers 2008