Refrigeration System - International comfort products N2H3 Installation Instructions Manual

R-22 split system heat pump
Hide thumbs Also See for N2H3:
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS

REFRIGERATION SYSTEM

A. COMPONENT MATCHES
Check to see that the proper system components are in
place, especially the indoor coil.
R-22 outdoor units can only be used with R-22 specific
indoor coils. If there is a refrigerant mis-match, consult
the indoor coil manufacturer to determine if a refrigerant
conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. If any other
type of metering device is installed on the indoor coil,
consult the indoor coil manufacturer to determine if a TXV
conversion kit is available.
CAUTION
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product
damage.
Indoor coil and outdoor unit must be listed as a
certified combination (match) in the ARI Unitary
Directory of Certified Products.
Indoor coil must have R-22 specific, TXV refriger‐
ant metering device.
When installing a TXV on an indoor coil, follow the
instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
Figure 3
Typical TXV Installation
EQUALIZER
TUBE
SENSING
BULB
HARD
SHUT-OFF
TXV
SENSING BULB
(EITHER SIDE)
SUCTION
É É É É
8 O'CLOCK
428 01 5001 00
INDOOR
COIL
SUCTION
TUBE
LIQUID
TUBE
STRAP
TUBE
É É É É
4 O'CLOCK
R-22 Split System Heat Pump
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure
maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line
Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet.
NOTE: A crankcase heater must be used when the
refrigerant line length exceeds 80 feet.
If outdoor unit is more than 10 feet higher than the indoor
coil, refer to the Extended Length Refrigeration Piping
Manual for instructions.
NOTE: When the outdoor unit is higher than the indoor
coil, the vertical separation must not exceed 100 feet.
NOTE: When the outdoor unit is lower than the indoor
coil, the vertical separation must not exceed 50 feet.
If it is necessary to add refrigerant line in the field, use
dehydrated
or
dry,
sealed,
refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing
until connections are ready to be made.
Be extra careful when bending refrigeration tubing.
Tubing can "kink" easily, and if this occurs, the entire
length of tubing must be replaced.
WARNING
!
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in
personal injury and/or death.
Relieve pressure and recover all refrigerant before
servicing existing equipment, and before final unit
disposal. Use all service ports and open all flow-
control devices, including solenoid valves.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improp‐
er product operation.
Do not leave system open to atmosphere any lon‐
ger than absolutely required for installation. Inter‐
nal system components - especially refrigerant
oils - are extremely susceptible to moisture con‐
tamination. Keep ends of tubing sealed during
installation until the last possible moment.
deoxidized,
copper
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

H2h3C2h3T2h3N2h4

Table of Contents