General Specifi Cations - American Standard GRWF130A94A0A Installation Manual

Direct vent gas fired with cast iron heat exchanger
Table of Contents

Advertisement

2.2 General Specifi cations - Table 1
Product Specifi cations
Model
Ratings
Input BTUH
DOE Output BTUH
Net (I=B=R®) Output BTUH
AFUE
Natural Gas Supply
Pilot gas orifi ce Qty X ID
Main gas orifi ces Qty X ID
Supply pressure (in. w.c.)
Manifold pressure (in. w.c.)
Flow rate BTUH
LP Gas Supply
Pilot gas orifi ce Qty X ID
Main gas orifi ces Qty X ID
Supply pressure (in. w.c.)
Manifold pressure (in. w.c.)
Flow rate BTUH
Heating
Max working temperature °F
Maximum working pressure (psig)
No. sections
No. burners
Boiler water content (gal.)
ASME Pressure Relief Valve (psi)
Dimensions, weights connections
Height (inches)
Width (inches)
Depth (inches)
Shipping Weight (lb.)
Net Weight (lb.)
Gas system connection
Heating water supply
Heating water return
Electrical power supply V / Ph / Hz
Minimum Circuit Ampacity (amps)
Maximum Overcurrent Protection
(amps)
* May be "A" or "T"
*GRWF130
130,000
110,000
96,000
84.3
1 x 0.40mm
3 x 3.10mm
7.0
3.6
130,000
1 x 0.24mm
3 x 1.90mm
11.0
10.6
130,000
230
60
4
3
3.06
30
33.46
19.69
24.21
364
320
1/2" NPT male
1" NPT male
1" NPT male
115 / 60 / 1
less than 2.0
15
18-CG02D1-4
7