American Standard GRWF130A94A0A Installation Manual page 32

Direct vent gas fired with cast iron heat exchanger
Table of Contents

Advertisement

4. Center the reset button in the hole and secure
with a locking nut. Use needle nose pliers. See
Figure 43.
5. Replace the reset button cover on the new manual
reset water temperature limit switch. See Figure 44.
Figure 44
18-CG02D1-4
32
Figure 43
6. Attach the wires removed earlier from the auto-
reset water temperature limit to the new manual
water temperature limit. See Figure 45.
Figure 45
7. Carefully unroll the capillary tube of the new
manual reset water temperature limit and feed the
sensing bulb through the strain relief clamp. See
Figure 46.
Figure 46