COMMON ALARM RELAY

The common alarm relay provides a set of contacts to drive a
customer provided external alarm indication. When the control
is powered up, if there are no Alarms, the relay contacts will
be OPEN. Any ALARM (not warning) will trigger the common
alarm relay to operate, closing the contacts. The connections
are made to the generator customer connection terminal strip
at Terminals 1 and 2 (Wires 209 and 210).
Specifications
Contact Rating:
10A at 250 VAC
Note: Contact rating is for resistive load only

CONNECTOR PIN DESCRIPTIONS

Figures 88 and 89, and Tables 19 and 20 provide the physical
pin connections as well as the Wire and circuit function.
8
7 6
15 14 13 12 11 10 9
23 22 21 20 19 18 17 16
Figure 88. J4 Connector (Harness Side)
Page 92
16
TO STARTER
13
TO CONTROLLER
CONNECTOR J4 - PIN 3
13
5A at 30 VDC
5 4
3
2
1
PART 4
Table 19. J4 Connector Pin Descriptions
PIN
WIRE
CIRCUIT FUNCTION
1
90
Switched to ground for choke solenoid operation
2
0
Common Ground (DC)
3
13
12 VDC un-fused for the controller
4
817
Grounded by the controller to turn on System
Ready (Green) LED
5
818
Grounded by the controller to turn on Alarm (Red)
LED
6
819
Grounded by the controller to turn on the
Maintenance (Yellow) LED
7
85
High temperature shutdown: Shutdown occurs
when Wire 85 is grounded by contact closure in
the oil temperature switch
8
820
Positive voltage (5VDC) for status LED's
9
14
12 VDC output for engine run condition. Used
for fuel solenoid and choke solenoid operation on
V-Twin Models
10
210
Common Alarm Relay Output
11
Not used
12
Not used
13
86
Low oil pressure shutdown: Shutdown occurs
when Wire 86 is grounded by loss of oil pressure
in the LOP switch
14
Not used
15
JMP 1 Installed in series with a resistor to identify the kW
to the controller
16
18
Ignition Shutdown: The controller grounds Wire
18 for ignition shutdown and receives a reference
signal for speed control while cranking and
running
17
56
12 VDC output to starter contactor relay/solenoid
18
209
Common Alarm Relay Output
19
194
Provides 12 VDC to the transfer relay (TR1)
20
23
Switched to ground (internally) to energize the
Transfer Relay
21
Not used
22
Not used
23
JMP 1 Installed in series with a resistor to identify the kW