Effekta MKD 1500 RT Operating Manual
Effekta MKD 1500 RT Operating Manual

Effekta MKD 1500 RT Operating Manual

Uninterrupted power supply
Hide thumbs Also See for MKD 1500 RT:

Advertisement

UPS
Uninterrupted Power Supply
MKD 1500 RT
Operating Manual V. 1.0
Article number:
Translation of the original operating manual
MKD 1500 RT: ACX11MKT1K500000

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MKD 1500 RT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Effekta MKD 1500 RT

  • Page 1 Uninterrupted Power Supply MKD 1500 RT Operating Manual V. 1.0 Article number: MKD 1500 RT: ACX11MKT1K500000 Translation of the original operating manual...
  • Page 2 Legal Notice Legal Notice by EFFEKTA Regeltechnik GmbH EFFEKTA Regeltechnik GmbH, 78628 Rottweil, retains the copyright to this documentation. This documentation is solely intended for the operator and his staff. The con- tent of this documentation (texts, figures, drawings, graphics, plans, etc.) may...
  • Page 3: Table Of Contents

    UPS MKD 1500 RT Table of Contents Table of Contents Introduction ......................5 Foreword ........................5 Validity ........................6 Storage ........................6 Symbols in this Manual ....................6 Information Obligation ....................10 Warranty Conditions ....................10 Transport and Storage ....................12 Positioning........................13 Safety Instructions ....................14 Introduction ......................14...
  • Page 4 UPS MKD 1500 RT Table of Contents Maintenance and Service ..................68 10.1 Measurement of the Bridging Period (Support Period) ..........68 10.2 Replacing the Accumulators ..................69 10.3 Service Report ......................70 10.4 Service Hotline......................71 10.5 Maintenance and Service Contracts................. 71 Technical Data .......................
  • Page 5: Introduction

    UPS MKD 1500 RT Introduction Introduction Foreword Dear Operator, You are about to operate an uninterrupted power supply. This operating manual should provide you with support for working responsibly and give you basic information about the uninterrupted power supply, namely how it operates, its application and what you should do in the event of malfunc- tioning.
  • Page 6: Validity

    Uninterrupted Power Supply defined in the Technical Data as a whole or they refer to modules, components and individual parts that were developed and built by EFFEKTA Regeltechnik GmbH.  11. Technical Data Storage This operating manual for the device must be stored in the vicinity of the device at all times so it is immediately available if need be.
  • Page 7 UPS MKD 1500 RT Introduction Text that is marked with WARNING! provides a warning about hazards. If accident prevention measures are not taken, these hazards may result in serious (irreversible) injuries or even death! Text that is marked with CAUTION! provides a warning about hazards. If accident prevention measures are not taken, these dangerous situations can lead to slight or medium reversible injuries.
  • Page 8 UPS MKD 1500 RT Introduction 1.4.2 Warning information 1.4.2.1 Warning about danger spots General warning about danger spots! 1.4.2.2 Specific warning Warning about dangerous electrical voltage! Warning for handling accumulators! 1.4.3 Instruction symbols Regard the provided documentation and/or instructions! Disconnect before work!
  • Page 9 UPS MKD 1500 RT Introduction 1.4.4 General symbols ● This dot marks descriptions of activities that you should carry out. – This dash marks specifications.  This arrow marks a cross reference. If a cross reference to another chapter is necessary in the text, this is short- ened for clarity.
  • Page 10: Information Obligation

    – cleaning and – disposal of the device. EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused by not or insufficiently trained staff! Warranty Conditions The receipt of delivery is considered as the record for the initial purchase and should be stored in a good place.
  • Page 11 EFFEKTA Regeltechnik GmbH does not provide either explicit or implicit war- ranties related to this device and its quality, performance, saleability or suitabil- ity for a certain purpose.
  • Page 12: Transport And Storage

    EFFEKTA Regeltechnik GmbH was informed about the possibility of such damage in advance. This exemption also includes any liability that can result from the claims of third parties against the initial purchaser.
  • Page 13: Positioning

    UPS MKD 1500 RT Introduction Positioning Do not install in an area in which combustible vapours result e.g. from petrol tanks, engine compartments, etc. The UPS is designed for operation in ventilated rooms with a surrounding tem- perature of 0 ° to 40 °C.
  • Page 14: Safety Instructions

    UPS MKD 1500 RT Safety Instructions Safety Instructions Introduction The UPS is a device produced for uninterrupted power supply in accor- dance with the technology rules and requirements. The device and its related components, modules and parts meet indi- vidually and in their entirety the currently valid safety standards as well as the standards of the EC Machinery Directive 2006/42/EC.
  • Page 15: Avoiding Personal Injury / Property Damage

    Only perform maintenance and service work that is described in the docu- mentation. Observe the required steps. Only use original replacement parts from EFFEKTA Regeltechnik GmbH. Protecting the Environment Send the product back to EFFEKTA Regeltechnik GmbH after the end of its use. We will ensure environmentally friendly disposal. MKD series...
  • Page 16: Connection

    UPS MKD 1500 RT Safety Instructions Connection Only connect the UPS to an earthed electric safety socket or be sure to connect it to the protective conductor in the event of a connecting termi- nal. Under no circumstances may the device may be operated without a protective conductor.
  • Page 17: Operation

    UPS MKD 1500 RT Safety Instructions Operation Before the loads are connected on the output, the basic configuration must be set. The output voltage in relation to the loads is very important. The UPS system includes energy storage (accumulators). As a result, the out- put can carry power even if the UPS is not connected on the mains input side.
  • Page 18: Maintenance, Service And Malfunctions

    UPS MKD 1500 RT Safety Instructions Defective accumulators must be disposed in an environmentally friendly way. Do not throw accumulators in household trash under any circumstances. Local disposal requirements are to be regarded. Maintenance, Service and Malfunctions Attention – Danger of electric shocks.
  • Page 19: Device Description Of Ups

    UPS MKD 1500 RT Device Description of UPS Device Description of UPS This manual is intended to provide basic information about single-phase offline UPS systems, namely how they function, the application of different functions and what you should do in the event of malfunctioning.
  • Page 20: Device Elements On The Front

    The front of the device contains all the operating and display elements required for normal operation. "Selection" key "Menu down / Next" key "Menu up / Back" key "ON / OFF" key Fig. 3-1 - 1 Front view of MKD 1500 RT MKD series...
  • Page 21: Lcd Display

    UPS MKD 1500 RT Device Description of UPS 3.1.1 LCD display Selection" key "Menu down / Next" key "Menu up / Back" key "ON / OFF" key Fig. 3-1 - 2 Operating element The LCD's background lighting changes colour depending on the device status.
  • Page 22 UPS MKD 1500 RT Device Description of UPS 3.1.2 Keys Selection Functions: Switch to the next sub-menu: Pressing this key for one second switches to the sub-menu of the menu item currently selected. Changes are not saved! Open the current menu: Pressing this key for one second opens the menu currently selected.
  • Page 23: Device Elements On The Back

    RS232 interface "DRY-OUT" connection Fig. 3-2 - 1 Back view of MKD 1500 RT The "UPS output" and "Mains input" plug connections are on potential mains when in the connected state. Even in an unconnected state, dangerously high voltage on the plug con- nections can result from the capacities charged within the device.
  • Page 24: Ups Output

    UPS MKD 1500 RT Device Description of UPS 3.2.1 UPS output IEC sockets 10 A for the connection of the loads. The protective conductor must be connected! Please always regard the indicated input voltage on the identification label or in the technical data of this manual.
  • Page 25: Communication Interface

    UPS MKD 1500 RT Device Description of UPS 3.2.3 DRY-IN and DRY-OUT connections The UPS has an integrated, individually programmable relay output with a po- tential-free contact for displaying the alarm remotely (potential-free output port) and a single signal input (potential-free input port). Please refer to the diagram on the rear of the UPS for the position of the ports.
  • Page 26 UPS MKD 1500 RT Device Description of UPS Fig. 3-2 - 3 Relay plug-in card Fig. 3-2 - 4 Terminal diagram for relay card MKD series...
  • Page 27: Usb Port

    UPS MKD 1500 RT Device Description of UPS 3.2.5 USB port The USB port is used to connect the UPS to a PC. 3.2.6 Fan for cooling the device. 3.2.7 Mains input IEC inlet connector 10A. This is connected to the mains using the connection cable with safety plug pro- vided.
  • Page 28: Device Modification

    UPS MKD 1500 RT Device Description of UPS Device modification The UPS can be installed in various ways. Vertically as a tower device on feet Horizontally in a 19" rack. Depending on the installation variant used, the LCD should be turned and the assembly bracket for the 19"...
  • Page 29 UPS MKD 1500 RT Device Description of UPS Process for turning display: Screws Fig. 3-3 - 2 Turning display - screws Remove the two screws (1). Carefully pull the front panel forwards and down away from the housing. The display is connected with a ribbon cable.
  • Page 30 UPS MKD 1500 RT Device Description of UPS Retaining screws for display Fig. 3-3 - 3 Retaining screws for display Remove the four screws (1). Turn the display 90° so that it sits correctly when the UPS is installed vertically.
  • Page 31 UPS MKD 1500 RT Device Description of UPS Fig. 3-3 - 4 Installing the UPS Place the UPS on the feet. The UPS can now be connected and started up. MKD series...
  • Page 32 UPS MKD 1500 RT Device Description of UPS 3.3.2 Modifying UPS as rack device Fig. 3-3 - 5 Rack device Follow these steps: Turn display to horizontal position. Fit retaining bracket. Fit UPS in plug-in element of 19" rack. MKD series...
  • Page 33 UPS MKD 1500 RT Device Description of UPS Process for turning display: Screws Fig. 3-3 - 6 Turning display - screws Remove the two screws (1). Carefully pull the front panel forwards and down away from the housing. The display is connected with a ribbon cable.
  • Page 34 UPS MKD 1500 RT Device Description of UPS Retaining screws for display Fig. 3-3 - 7 Retaining screws for display Remove the four screws (1). Turn the display 90° so that it sits correctly when the UPS is installed hori- zontally.
  • Page 35 UPS MKD 1500 RT Device Description of UPS Fig. 3-3 - 9 19" rack Slide the UPS into the plug-in shaft of the 19" rack. MKD series...
  • Page 36 UPS MKD 1500 RT Device Description of UPS Screws Fig. 3-3 - 10 Fastening UPS in 19" rack Fit the UPS by fastening with screws (1). The UPS can now be connected and started up. MKD series...
  • Page 37: Storage And Unpacking

    UPS MKD 1500 RT Storage and Unpacking Storage and Unpacking Storage of the UPS If the device is not installed immediately, please consider the following: Always store the device and its accessories in the original packaging. Recommended surrounding temperatures for storage are: + 0 °C ...
  • Page 38: System Description

    UPS MKD 1500 RT System Description System Description The UPS operates continuously following the double converter principle. It pre- pares the mains current and provides an uninterrupted and fault-free, single- phase voltage for the loads critical to operation. In addition to supplying the loads, the device also keeps the internal accumula- tors charged.
  • Page 39 UPS MKD 1500 RT System Description If the mains failure exceeds the bridging period of the UPS, this switches off to prevent deep discharge of the accumulators. With the return of mains voltage, the UPS starts up again automatically, supplies the loads and controls charging of the accumulator bank.
  • Page 40: Installation And Connection Of The Ups

    UPS MKD 1500 RT Installation and Connection of the UPS Installation and Connection of the All the requirements stated in the technical data for the surrounding and opera- tional conditions are to be observed to ensure the perfect operation of the UPS.
  • Page 41 UPS MKD 1500 RT Installation and Connection of the UPS Mains 16 A 1.5 mm Load 1 Load 2 Fig. 6-1 - 1 Connection of the UPS and loads MKD series...
  • Page 42: Ups Communication Connection

    UPS MKD 1500 RT Installation and Connection of the UPS UPS communication connection To exchange data with the UPS, there is a convenient communication inter- face. Only one communication port can be active at any one time. The USB port takes priority over the RS232 port.
  • Page 43: Connection Sequence

    UPS MKD 1500 RT Installation and Connection of the UPS Connection Sequence Connect the UPS with the mains, and make sure the mains and the UPS are shut off during the process. Before the loads are connected on the output, the basic configuration must be set.
  • Page 44 UPS MKD 1500 RT Installation and Connection of the UPS The relay output contact must not be connected to circuits which are linked to the supply mains. Supply cables must have reinforced insulation. The relay output contact has a maximum load bearing capacity of 30 V AC/1 A and nominal values of 60 V DC/2 A.
  • Page 45 UPS MKD 1500 RT Installation and Connection of the UPS 6.3.2 Assignment of the EPO connection Conductor Connection wire size Recommended wire function size 4 - 0.32 mm 0.82 mm (18 AWG) (12 - 22 AWG ) Leave the EPO plug installed on the EPO port of the UPS, even if the EPO function isn't needed.
  • Page 46: Device And Its Operation

    UPS MKD 1500 RT Device and its Operation Device and its Operation Operating the UPS The operation of this system is characterised by various types of operations and messages. 7.1.1 Operating mode Line mode "Line mode" is the normal mains mode for the UPS.
  • Page 47 UPS MKD 1500 RT Device and its Operation Bypass mode In bypass mode, the UPS has no backup function. The UPS switches to bypass mode in the event of an inverter problem for ex- ample. The mains input and the mains output are bridged using a relay.
  • Page 48 UPS MKD 1500 RT Device and its Operation HE (High Efficiency) mode In HE mode, the UPS initially enters bypass mode. The inverter is only acti- vated in the event of mains failure. It takes just milliseconds to switch over.
  • Page 49 UPS MKD 1500 RT Device and its Operation Warning Warnings are not usually fatal errors but should be rectified as quickly as possible. The UPS continues to function in the event of a warning. If there are warnings active on the UPS, this is indicated on the display as follows.
  • Page 50 UPS MKD 1500 RT Device and its Operation Other messages In the event of an overload, the UPS issues an acoustic signal. The alarm sounds twice a second. In the event of an overload, the display is as follows: Fig. 7-1 - 9 During a battery test, the display is as follows: Fig.
  • Page 51: Operating Manual For The Ups

    UPS MKD 1500 RT Device and its Operation If an error is detected on the accumulator, e.g. "Battery not connected" or "Poor battery status", the display is as follows: Fig. 7-1 - 11 Battery error Operating Manual for the UPS The operator of this UPS system must always observe the instructions in this manual.
  • Page 52 UPS MKD 1500 RT Device and its Operation 7.2.1 Switching the UPS on and off Switching the UPS on with connected loads: Before switching the UPS on, check that all loads are correctly connected. Switch the UPS on. You know that the UPS is being powered up when the fan is switched on and a welcome message appears on the LCD.
  • Page 53 UPS MKD 1500 RT Device and its Operation 7.2.2 UPS menu structure UPS status -> Status of the UPS Event Log -> Error message Measurements -> Measurements Control -> Control menu Identification -> Identification Settings -> Settings Main menu Standard display Status display Fig.
  • Page 54 UPS MKD 1500 RT Device and its Operation If the display is in its standard setting, you can navigate within the status dis- plays by briefly pressing the two arrow keys. Pressing and holding down the "Menu up / Back" key takes you from the stan- dard display to the main menu.
  • Page 55: Menu

    UPS MKD 1500 RT Device and its Operation Menu 7.3.1 UPS status menu Pressing the "Menu up / Back" key (Fig. 3-1 - 2, Pos. 4) for more than one second takes you from the standard display to the main menu.
  • Page 56: Status Messages

    UPS MKD 1500 RT Device and its Operation 7.3.2 Status messages Pressing the "Menu up / Back" key (Fig. 3-1 - 2, Pos. 4) for more than one second takes you from the main menu to the corresponding sub- menu.
  • Page 57 UPS MKD 1500 RT Device and its Operation 7.3.3 Measurements Pressing the "Menu up / Back" key (Fig. 3-1 - 2, Pos. 4) for more than one second takes you from the main menu to the corresponding sub- menu. Briefly pressing the "Selection" key (Fig. 3-1 - 2, Pos. 2) takes you from the current sub-menu back to the main menu.
  • Page 58 UPS MKD 1500 RT Device and its Operation 7.3.4 Control menu Pressing the "Menu up / Back" key (Fig. 3-1 - 2, Pos. 4) for more than one second takes you from the main menu to the corresponding sub- menu.
  • Page 59 UPS MKD 1500 RT Device and its Operation 7.3.5 Identification Pressing the "Menu up / Back" key (Fig. 3-1 - 2, Pos. 4) for more than one second takes you from the main menu to the corresponding sub- menu. Briefly pressing the "Selection" key (Fig. 3-1 - 2, Pos. 2) takes you from the current sub-menu back to the main menu.
  • Page 60 UPS MKD 1500 RT Device and its Operation 7.3.6 Settings Fig. 7-3 - 6 Settings The Settings menu is password protected. The password is "USER". In the Settings menu you can set all the UPS parameters, such as the pass- word, acoustic signals, voltage values, frequencies, etc.
  • Page 61 UPS MKD 1500 RT Device and its Operation Contact your specialist dealer before you change the settings in this menu. Incorrect settings may result in malfunctions or even UPS destruc- tion. The table below contains a description of the individual parameters.
  • Page 62 UPS MKD 1500 RT Device and its Operation Parameter Possible settings Default value <enable><disable> enable Automatic overload restart <enable> means that the UPS switches from bypass mode to normal mode once the batter- ies have been 70 % charged. Auto bypass <enable><disable>...
  • Page 63 UPS MKD 1500 RT Device and its Operation Parameter Possible settings Default value Set running time Day:0000-9999 Day:0000 Hour:00-23 Time:00:00:00 Minute:00-59 Second:00-59 LCD contrast <-5>……..<+5> The LCD contrast can be set here from – 5 to + 5. MKD series...
  • Page 64: Eliminating Errors

    UPS MKD 1500 RT Eliminating Errors Eliminating Errors Only authorised professional staff are to perform work for eliminating er- rors on the UPS system. Error message Possible cause Remedy No input voltage No display and no Check the mains socket and the sup- warning sound even ply cable.
  • Page 65 UPS MKD 1500 RT Eliminating Errors Error message Possible cause Remedy Contact your dealer. Maintain battery The battery may Alarm code: 13 need replacing. Overload Overload Check the loads and disconnect a few Alarm code: 41/42/43 loads that are not essential.
  • Page 66 UPS MKD 1500 RT Eliminating Errors If the UPS error you have observed cannot be found in the table, please inform our service team and have the following information at your disposal: 1. Model number, serial number 2. Date on which the problem occurred 3.
  • Page 67: Software

    UPS MKD 1500 RT Software Software A suitable software package can determine and process the settings and the operating states of the UPS via the communication interface. The software packages are available from the manufacturer / dealer or under the provided service hotline. You will receive useful information about the suited software packages with regard to your application and the UPS.
  • Page 68: Maintenance And Service

    UPS MKD 1500 RT Maintenance and Service Maintenance and Service You can assume a long service life and uninterrupted operation with minimum maintenance for your UPS system. The reliability of the UPS will however be determined primarily by the surround- ing conditions.
  • Page 69: Replacing The Accumulators

    UPS MKD 1500 RT Maintenance and Service Remember that the accumulators of the system are discharged after the measurement, which means that the UPS system must work for a few hours (at least 5 hours) in the mains and charging operation before it is ready for use again at approx.
  • Page 70: Service Report

    UPS MKD 1500 RT Maintenance and Service 10.3 Service Report Always enter all the maintenance and service work that has been performed on the UPS system in the service report. Date Executed work Performed by MKD series...
  • Page 71: Service Hotline

    10.5 Maintenance and Service Contracts EFFEKTA Regeltechnik GmbH offers you appropriate maintenance and other services to ensure the greatest possible reliability and availability of the UPS system. We can also support and help you in the following areas with our pro-...
  • Page 72: Technical Data

    UPS MKD 1500 RT Technical Data Technical Data MKD model 1500 RT Power Power in VA 1500 Power in W 1350 Bridging time Nominal load 5 minutes Input Nominal voltage 230 V AC Input frequency range (45~55) / (54~66) Hz...
  • Page 73: Scope Of Delivery / (Optional) Accessories

    Scope of Delivery / (Optional) Accessories In the following, you will find a list of components that are specially approved and tested by EFFEKTA Regeltechnik GmbH for this UPS (please check the completeness of the delivery immediately after receiving the goods).
  • Page 74: Wear Parts List

    UPS MKD 1500 RT Technical Data 11.1.2 Communication interfaces / (optional accessories) Description Article number Relay plug-in card ZOC/AS400 SNMP mini slot plug-in card GE/32CS121MINI 11.2 Wear Parts List The components listed in the following are subject to normal aging and are not...
  • Page 75: Requirements From The Declaration Of Conformity

    UPS MKD 1500 RT Requirements from the Declaration of Conformity Requirements from the Declaration of Conformity The CE-labelled UPS to the following EU directives and harmonised standards: EU directives: LVD 2006/95/EC EMC 2004/108/EC Harmonised standards: EN 62040-1-1:2003 EN 62040-2:2006 You can receive an EU declaration of conformity for products with a CE label...
  • Page 76 EFFEKTA Regeltechnik GmbH Rheinwaldstraße 34 D – 78628 Rottweil...

Table of Contents