10. BOILER DIMENSIONS & RATINGS
Figure 10.1: Boiler Views
Table 10.2: Series PSC II™ Boiler Ratings
Boiler
Model
Number
PSCII-03
PSCII-04
PSCII-05
PSCII-06
1 Net I=B=R water ratings based on an allowance of 1.15.
2 Consult factory before selecting a boiler for installations having unusual piping and pickup
requirements, such as intermittent system operation, extensive piping systems, etc.
3 Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S.
Government test.
Table 10.1: Series PSC II™ Boiler Dimensions
SERIES PSC II™ BOILER DIMENSIONS
Boiler
Model
Number
PSCII-03
PSCII-04
PSCII-05
PSCII-06
SERIES PSC II™ BOILER RATINGS
DOE Heating
Input
Capacity
MBH
kW
MBH
65
19
56
90
26
77
120
35
102
150
44
128
BOILER DIMENSIONS & RATINGS
Jacket Width "A"
12-1/2"
318 mm
15-7/8"
403 mm
19-1/4"
489 mm
22-5/8"
575 mm
Net I=B=R
Seasonal
3
1,2
Ratings Water
Efficiency
(AFUE)%
kW
MBH
kW
16
49
14
23
67
20
30
89
26
37
111
32
Water Content
3
Gallon
Liter
86.0
4.72
17.87
85.0
6.00
22.71
85.0
7.28
27.56
85.1
8.56
32.40