Technical Specifications - Meta System ARCHIMOD 20 Operating And Maintenance Manual

Table of Contents

Advertisement

2.4
GENERAL CHARATERISTICS
Rated Power:
Active Power:
Technology:
Configuration I/O:
UPS architecture:
INPUT CHARACTERISTICS
Maximum current
(tri/tri):
Maximum current
(tri/single):
Maximum current
(single/tri):
Maximum current
(single/single):
Input nominal voltage:
Input frequency:
Input connections:
THD input current:
Input power factor:
OUTPUT CHARACTERISTICS
Maximum
current (tri/tri):
Maximum
current
(tri/single):
Maximum
current
(single/tri):
Maximum
current
(single/single):
Output nominal voltage:
Output nominal frequency:
Output connections:
Efficiency:
- Mains (On Line)
- Mains (Eco mode)
Over load:
Factor crest
Technological
Description
2-6

TECHNICAL SPECIFICATIONS

20 KVA
40 KVA
16 KW
(Only Archimod 20/40KVA can be configured single/single, single/tri, tri/single, tri/tri by user)
37 A
37 A
111 A
111 A
(Only Archimod 20/40KVA V = 230 V +15% -20% with single input)
28,99 A
57,98 A
86,96 A
28,99 A
86,96 A
(Only Archimod 20/40KVA V = 230 V ± 1% with single output)
60 KVA
32 KW
48 KW
On Line, double conversion VFI – SS - 111
Triphase / Triphase
Modular with 6,7 KVA power modules (cos
Housed in a single cabinet. Expendable, redundant N+X
(except for Archimod 120KVA).
74 A
111 A
-
-
-
-
-
-
V = 400
(Tri + N)
Hz = 50 / 60 +/- 2%
86,97 A
-
-
-
-
-
-
V = 400 +/- 1%
125% for 10 min - 150% for 1 min
Operating and Maintenance Manual
80 KVA
100 KVA
64 KW
80 KW
Ê
0,8).
148 A
185 A
-
-
-
-
-
-
+ 15% - 20%
Tri + Neutral
< 3%
> 0.99
115,96 A
144,95 A
-
-
-
-
-
-
Hz = 50/60 sincronized
Trifase + Neutro
95%
99%
3,5:1
code 504275001 Rev. September 2010
120 KVA
96 KW
222 A
-
-
-
173,94 A
-
-
-