Inspections, Tests And Maintenance; Air / Vacuum Vent - Viking ESFR Technical Data Manual

Pre-primed single interlock preaction cold storage system
Hide thumbs Also See for ESFR:
Table of Contents

Advertisement

March 7, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
H. Inspections, Tests and Maintenance
Problem
Possible Causes
1) Power disconnected.
Unit will not turn on.
2) Blown fuse.
1) No power to unit.
Pump does not operate
2) Liquid level in tank low.
in Automatic mode when
3) Magnetic starter overload tripped.
CS-1 pressure drops.
4) Time delay active.
5) Pump motor defective.
1) Pump operates on manifold
Pump does not operate
pressure, not system pressure. System
in Automatic mode when
pressure switch setting is higher than
system valve opens.
the CS-1 pressure switch setting.
1) Supply container empty.
2) Incorrect valve position.
3) Pump rotation backward.
4) Insuffi cient head pressure to pump
Failure to pump.
inlet.
5) Pump not up to speed.
6) Clogged suction line.
7) Air in suction line.
Excessive power
1) Pump not fully broken in.
consumption.
2) Mechanical damage.
Other pump-related
If other pump related problems are suspected, call the Viking Technical Services Department at 1-877-384-
problems.
5464.
Pump stops before
Discharge pipe is too small or there is a
desired system pressure.
buildup of back pressure.

11. Air / Vacuum Vent

The Viking AV-1 device is a float operated automatic
air vent that is installed at high points of the sprinkler
system where air pockets can accumulate. As the sys-
tem fills, air is automatically vented through the orifice
of the vent valve. When the system is full, the water or
antifreeze solution raises the float due to buoyancy and
shuts off the outlet orifice. As air throughout the system
accumulates at the high points of system piping, it will
be automatically expelled to provide air-free system
piping.
Airflow during venting is restricted due to differential pressure across vent orifice. It is recom-
mended to slow fill the system initially to minimize the buildup of air in the system. See Table
16 for air flow capacity at various differential pressures.
Having the AV-1 installed on the end of each high-point branch line and/or main provides quick-
er and more complete drainage of system piping. This is because during drainage of system
piping, the AV-1 will open and allow air to enter and break the vacuum inside the piping.
TECHNICAL DATA
Table 15 - Troubleshooting Guide
Remedies
1) Check power at supply and unit, and correct.
2) Check fuses, replace as required, and determine cause of blown
fuse.
1) Verify power at unit terminal block.
2) Fill tank to proper height.
3) Verify and fi x cause of overload. Press reset button on starter.
4) Wait 10 minutes for time delay to time out. Correct leaks in
system.
5) Replace.
1) Verify system pressure switch setting is correct. The CS-1
pressure switch setting must not be adjusted higher. Adjust CS-1
switch setting lower if approved by factory.
1) Connect full supply container.
2) Correct valve position per instructions.
3) Correct pump rotation.
4) Raise supply container.
5) Check voltage.
6) Inspect and clean Y-Strainer.
7) Check for air in pump suction line.
1) Pump normally draws higher current during break-in period. This
condition will work itself out after several weeks.
2) Turn pump over by hand. If there are tight spots after break-in,
call Technical Services.
1) Increase pipe size.
2) Increase dS1 setting on pump switch.
3) Make sure dr1 setting is set to 0.50.
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM
Page 53