Viking ESFR Technical Data Manual page 46

Pre-primed single interlock preaction cold storage system
Hide thumbs Also See for ESFR:
Table of Contents

Advertisement

Page 46
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Dielectric unions, if needed, are installed between the pump station piping and system
piping.
All piping to and from the pump station is independently supported and does not place
any strain on the unit's piping.
Power supplied to the unit is appropriate.
Pump rotation has been checked and is correct.
System inputs are connected according to the electrical schematic. All pressure
switches are set or programmed correctly.
Air can be vented from the system when filling with antifreeze.
TECHNICAL DATA
Figure 33 - Flow Diagram
March 7, 2008
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM