Tank & Pump Unit; Description - Viking ESFR Technical Data Manual

Pre-primed single interlock preaction cold storage system
Hide thumbs Also See for ESFR:
Table of Contents

Advertisement

Page 42
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
10. CS-1 Tank & Pump Unit
A. Description
The Viking CS-1 Tank and Pump Package is an integrated storage tank and pumping system.
The tank and pump system automatically maintains the supervisory solution pressure in the
piping system above the supervisory alarm pressure until the detection system and sprinkler
is activated. The pump uses propylene glycol solution in the storage tank to maintain system
pressure and make up for minor system leaks.
The system is designed to accept up to 50% propylene glycol and water premix solution. It is
recommended that certified premix be used. Do not mix different antifreeze solutions within
the system.
WARNING: Motors, electrical equipment, and controls can cause electrical arcs that will
ignite a flammable gas or vapor. Never operate or repair in or near a flammable gas,
vapor, excessive dust or steam. Never store flammable liquids or gases near the unit.
Safety:
This equipment is designed to be safe in the use for which it was planned, provided it is
installed, started up, operated, and maintained in accordance with the instructions in this
manual. Therefore, all personnel who install, use, or maintain the equipment must under-
stand this manual. The unit contains electrical components that operate at line voltage and
moving parts. Before working on the unit, isolate and lock it out from the electrical supply.
All maintenance operations must be performed by qualified persons who have knowledge
in the necessary precautions.
US Power Supply Option (60 Hz)
Part
Risers
Number*
65 gal
13050-1
1
(246 L)
65 gal
13050-2
2
(246 L)
160 gal
13050-3
3
(606 L)
160 gal
13050-4
4
(606 L)
160 gal
13050-5
5
(606 L)
160 gal
13050-6
6
(606 L)
US Power Supply Voltage suffixes:
A = 208 V, B = 230 V, C = 460 V, D = 575 V.
*Add voltage suffix after part number
TECHNICAL DATA
Table 7 - Ordering Information
Tank
Solenoid
Control
Size
Valves
Relays
1
2
3
4
5
6
International Power Supply Option (50 Hz)
Part
Risers
Number*
1
13051-1
1
2
13051-2
2
3
13051-3
3
4
13051-4
4
5
13051-5
5
6
13051-6
6
International Power Supply Voltage suffixes:
E = 380V
The pump furnished in all units is 3 HP, 3 Phase.
March 7, 2008
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM
Tank
Solenoid
Size
Valves
65 gal
1
(246 L)
65 gal
2
(246 L)
160 gal
3
(606 L)
160 gal
4
(606 L)
160 gal
5
(606 L)
160 gal
6
(606 L)
Control
Relays
1
2
3
4
5
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents