Table of Contents

Advertisement

Page 26
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com

4. Designing the Detection System

The detection system shall consist of low temperature "spot" type heat detectors, air sampling
smoke detection or beam smoke detection. Linear heat detection is not suitable for this system
and shall not be used.
Viking does not have a preferred manufacturer of initiating devices. Spot heat detectors are
typically not subject to compatibility issues with the release control panel. Viking considers all
listed and approved spot type heat detectors that the manufacturer determines is appropriate for
cold storage applications acceptable. The detection system shall be designed to allow the heat
detectors to operate prior to the Viking K25.2 ESFR sprinklers by selecting a lower temperature
rating and RTI for the heat detector. (NFPA 13 defines an ESFR Sprinkler as having a thermal
element with an RTI of 50 (meters sec.
tacted for the heat detector RTI information.
Air sampling systems are also considered acceptable for activation of the ESFR Cold Storage
System, and should be designed in accordance with the manufacturer's instructions.
The detection system shall be designed in accordance with the requirements of NFPA 72.
5.6.2.3 Marking: Heat-sensing fire detectors shall be marked with their listed operating tempera-
ture. Spot-type heat detectors shall also be marked with their RTI (response time index). The
RTI marking requirements shall have an effective date of July 1, 2008.
5.6.5.5.1 On ceilings 10 ft to 30 ft (3 m to 9.1 m) high, heat detector linear spacing shall be
reduced in accordance with Table 5.6.5.5.1 prior to any additional reductions for beams, joists,
or slope, where applicable.
5.6.5.5.2 The minimum spacing of heat detectors shall not be required to be less than 0.4 times
the height of the ceiling.
Table 5.6.2.1.1 Temperature Classifi cation for Heat-Sensing Fire Detectors
Temperature
Classifi cation
Low*
Ordinary
Intermediate
High
Extra high
Very extra high
Ultra high
*Intended only for installation in controlled ambient areas. Units shall be marked to indicate maximum ambient installation
temperature.
TECHNICAL DATA
½
) or less.) The heat detector manufacturer shall be con-
Table 4 - Detector Classification from NFPA 72
Temperature Rating Range
° F
° C
100-134
39-57
135-174
58-79
175-249
80-121
250-324
122-162
325-399
163-204
400-499
205-259
500-575
260-302
ESFR PRE-PRIMED SINGLE
INTERLOCK PREACTION
COLD STORAGE SYSTEM
Maximum Ceiling Temperature
° F
° C
80
28
115
47
155
69
230
111
305
152
380
194
480
249
March 7, 2008
Color
Code
Uncolored
Uncolored
White
Blue
Red
Green
Orange