Viking ESFR Technical Data Manual page 48

Pre-primed single interlock preaction cold storage system
Hide thumbs Also See for ESFR:
Table of Contents

Advertisement

Page 48
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Single Riser
Two Risers
Three Risers
Four Risers
Five Risers
Six Risers
Inputs
Input 1
"Manual" position of Hand-Off- Auto Switch
Input 2
"Auto" position of Hand-Off- Auto Switch
Input 3
Pressure Switch of Pumping Unit
Input 4
Tank Level Switch
Input 5
System 1 Inputs
Input 6
System 2 Inputs
Input 7
System 3 Inputs
Input 8
System 4 Inputs
Input 9
System 5 Inputs
Input 10
System 6 Inputs
Input 11
Switch A – Down Position
Input 12
Switch A – Up Position
Input 13
Switch B – Down Position
Input 14
Switch B – Up Position
Output
"Power On"
Output 1 on when: Input 1 or Input 2 are on.
1
light
Pump Motor
Output
Output 2 on when: (Manual Mode System and
Starter Coil and
2
Tank Filling) Input 1 on + Input 3 on.
"Pump" light
Output 3 on when: (Manual Mode) Input 1 on and
Output
System 1
Input 5 on and Input 12 on and Input 13 off and
3
Solenoid Valve
Input 14 off.
Output 4 on when: (Manual Mode) Input 1 on and
Output
System 2
Input 6 on and Input 11 on and Input 13 off and
4
Solenoid Valve
Input 14 off.
Output 5 on when: (Manual Mode) Input 1 on and
Output
System 3
Input 7 on and Input 11 off and Input 12 off and
5
Solenoid Valve
Input 14 on.
Output 6 on when: (Manual Mode) Input 1 on and
Output
System 4
Input 8 on and Input 11 off and Input 12 off and
6
Solenoid Valve
Input 13 on.
Output 7 on when: (Manual Mode) Input 1 on and
Output
System 5
Input 9 on and Input 12 on and Input 14 on.
7
Solenoid Valve
Output
System 6
Output 8 on when: (Manual Mode) Input 1 on and
8
Solenoid Valve
Input 10 on and Input 11 on and Input 13 on.
Output
Level Switch
Output 9 on when: Input 4 on.
9
Relay Coil
TECHNICAL DATA
Table 9 - CS-1 Schematic Drawing Numbers
Drawing Number
60Hz
13050-1
13050-2
13050-3
13050-4
13050-5
13050-6
Table 10 - Inputs and Outputs
Table 11 - Control Logic
ESFR PRE-PRIMED SINGLE
Manual Page
50Hz
60Hz
13051-1
60-61
13051-2
62-63
13051-3
64-65
13051-4
66-67
13051-5
68-69
13051-6
70-71
Output 1
"Power On" light
Output 2
Pump Motor Starter Coil and "Pump" light
Output 3
System 1 Solenoid Valve
Output 4
System 2 Solenoid Valve
Output 5
System 3 Solenoid Valve
Output 6
System 4 Solenoid Valve
Output 7
System 5 Solenoid Valve
Output 8
System 6 Solenoid Valve
Output 9
Level Switch Relay Coil
(Automatic Mode) Input 2 on + Input 3 on + Input
4 on +
And Internal Timer times to 10 minutes. The timer
-or-
begins when Manual or Automatic mode is started
and is reset when pump turns off in Automatic
Mode.
-or-
(Automatic Mode) Input 2 on and Input 5 on.
(Automatic Mode) Input 2 on and Input 6 on.
-or-
(Automatic Mode) Input 2 on and Input 7 on.
-or-
-or-
(Automatic Mode) Input 2 on and Input 8 on.
(Automatic Mode) Input 2 on and Input 9 on.
-or-
-or-
(Automatic Mode) Input 2 on and Input 10 on.
March 7, 2008
INTERLOCK PREACTION
COLD STORAGE SYSTEM
50Hz
72-73
74-75
76-77
78-79
80-81
82-83
Outputs