Display on V5 All-in-one board
Blink
Fault Message
Counts
1
IPM fault
3
Outdoor coil sensor fault
5
Exhaust temperature sensor fault
7
Compressor drive fault
9
Outdoor overheat protection
11
AC overcurrent protection
13
Compressor top temperature protection
15
Voltage protection
17
Exhaust Overpressure Protection
19
Indoor overheat protection
21
Outdoor EEPROM fault
23
Outdoor DC fan fault
25
Model configuration wrong
27
Reserved
29
Reserved
V5 All-in-one board
Blink
Counts
Short-circuit / open-circuit fault of
2
outdoor temperature sensor
4
Absorption temperature sensor fault
6
Current sensor fault
8
Compressor drive protection
10
IPM protection
12
Exhaust Temperature Protection
14
Exhaust Overtemperature Protection
16
Exhaust underpressure protection
18
Indoor antifreeze protection
20
Indoor / outdoor communication fault
Outdoor
22
protection
24
Outdoor coil overheat protection
26
Indoor fan fault
28
Reserved
30
Reserved
7
Fault Message
ambient
overtemperature