Service Data; Maintenance - McLean Cooling Technology LOBOY 16 Instruction Manual

Table of Contents

Advertisement

SERVICE DATA

LB16 Series Component List
Part Description
Blower Motor, Condenser
Blower Motor, Evaporator
Capacitor, Condenser Blower
Capacitor, Evaporator Blower
Capacitor, Compressor, Run
Time Delay Relay
Coil, Condenser
Coil, Evaporator
Compressor
Contactor, Compressor
Evaporator Inlet Filter
Filter/Dryer
Capillary Tube
Thermostat

Maintenance

Compressor
The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should
provide years of satisfactory operating service.
Condenser and Evaporator Blower Motors
Blower motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life
of the motor.
Caution: Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly
deteriorate condenser coils, blowers and motors, etc. Contact McLean Cooling for special recommendations.
Refrigerant Loss
Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks.
Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment
during manufacture may require repair or recharging of the system. This work should only be performed by
qualified professionals, generally available through a local, reputable air conditioning repair or service company.
Should the refrigerant charge be lost, access ports on the suction and discharge sides of the compressor are
provided for recharging and/or checking suction and discharge pressures. Under no circumstances should the
access fitting covers be loosened, removed or tampered with. Breaking of seals on compressor access fittings
during warranty period will void warranty on hermetic system. Recharging ports are provided for the ease and
convenience of reputable refrigeration repair service personnel for recharging the air conditioner
Refer to the data on the nameplate that specifies the type of refrigerant and the charge size in ounces.
Before recharging, make sure there are no leaks and that the system has been properly evacuated into a
deep vacuum. Technician must weigh in charge according to the nameplate specifications.
Page 8
Part Number
10-1020-04
10-1020-10
52-6083-00
52-6084-05
52-6031-01
10-1005-71
16-7001-00
52-6121-01
10-1026-115
10-1005-42
10-1000-08
52-6028-00
99-0640-35
52-6155-02
.
10-1008-177 Rev 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Loboy lb16-1026-g series

Table of Contents