TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER ................................3 HANDLING AND TESTING THE AIR CONDITIONER ..........................3 HOW TO READ MODEL NUMBERS ................................3 DIMENSIONAL DRAWINGS ..................................... 4 4000 BTU 115V ......................................4 6000 and 4000 BTU 230V ..................................4 INSTALLATION INSTRUCTIONS ..................................
RECEIVING THE AIR CONDITIONER Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Technical Products -- within 15 days of delivery.
DIMENSIONAL DRAWINGS 4000 BTU 115V COOLING/HEATING THERMOSTATS POWER INLET WARM ENCLOSURE AIR OUT AIR IN REMOVABLE HANGING TABS AMBIENT AIR IN COOL AIR OUT ACCESS PANEL FOR OPTIONAL HEATER 89076942 1/4-20 UNC (11) CLEANABLE, REUSABLE, MOUNTING HOLES ALUMINUM INLET FILTER BEHIND REMOVABLE PANEL NOTE: 1.
INSTALLATION INSTRUCTIONS 1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See HANDLING AND TESTING THE AIR CONDITIONER on page 3. 2. Using the mounting gasket kit provided with the unit, install gaskets to the air conditioner, see Figure 1. 3.
TECHNICAL INFORMATION Sequence of Operation The air conditioner comes standard with two internally mounted thermostats. There are two modes of operation; heating and cooling. During heating and cooling modes the evaporator fan will be running. Heating When the enclosure temperature is below the heating thermostat setpoint, power is applied to the heaters. When the enclosure temperature is 10 degrees above the setpoint the heater is powered off.
6000 BTU Unit Characteristics Model G280616GXXX G280626GXXX Dimensional Data Height 28.55 / 725.1 mm Width 16.97 / 431.1mm Depth 10.10 / 256.6mm Unit Weight 84 lbs / 38 kg Unit Protection Rating Type 12/4/4X/3R Cooling Data Refrigerant R407C Refrigerant Charge 20 oz.
6000 BTU 1-Phase Wire Diagram (actual unit options may vary) SUPPRESSOR (OPTIONAL) TO CUSTOMER SWITCH THERMAL DISPLAY (OPTIONAL) TO THERMAL DISPLAY TRANSFORMER RELAY MALFUNCTION SWITCH (OPTIONAL) DOOR SWITCH (OPTIONAL) HEAD PRESSURE CONTROL LEAD COOLING THERMOSTAT HEATING THERMOSTAT POWER BLOCK HEATER LIMIT SWITCHES EVAPORATOR...
4000 BTU 1-Phase Schematic SUPPRESSOR (OPTIONAL) TRANSFORMER WITH TEMPERATURE DISPLAY (OPTIONAL) CUSTOMER SWITCH EVAPORATOR FAN COMPRESSOR HEATER (OPTIONAL) DOOR SWITCH TRANSFORMER AND RELAY (OPTIONAL) THERMOSTAT HEATING, LIMIT SWITCHES AND HEATER THERMOSTAT COOLING AMBIENT IMPELLER WITH HEAD PRESSURE CONTROL (OPTIONAL) START RELAY START CAPACITOR COMPRESSOR AND OVERLOAD...
MAINTENANCE Compressor The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should provide years of satisfactory operating service. Under no circumstances should the access fitting covers be loosened, removed or tampered with. Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system. Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner.
Condenser and Evaporator Air Movers Impeller motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life of the motor. If one of the condenser impeller motors (ambient impellers) should fail, it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower.
TROUBLE SHOOTING Basic Air Conditioning Trouble Shooting Check List 1. Check manufacturer’s nameplate located on the unit for correct power supply. 2. Turn on power to the unit. The evaporator (Enclosure or “COLD” air) impeller should come on. Is there airflow? YES, proceed to step 3.
Symptoms and Possible Causes: SYMPTOM POSSIBLE CAUSE Clogged fins on coil(s) Dirty filter Impellers not running Unit won’t cool Compressor not running Compressor runs, but has bad valves Loss of refrigerant Low line voltage at start. Should be +/-10% rated voltage. Compressor motor stuck Compressor tries to start but won’t run Bad contactor...
WARRANTY Pentair Technical Products warrants that the Goods manufactured by Pentair Technical Products will be free from defects in material and workmanship for a period of one (1) year from the date of shipment by Pentair Technical Products, subject to the following conditions and exclusions: A.
1. Complete Model Number, Serial Number and description of damaged unit being returned. 2. Original Buyer Purchase Order number and date product was received by Buyer. 3. Quantity to be returned and a brief description of failure for each unit, if different. 4.