Stanley Brandon Dry Installation And Commissioning Instructions
Stanley Brandon Dry Installation And Commissioning Instructions

Stanley Brandon Dry Installation And Commissioning Instructions

Advertisement

Quick Links

Brandon
Dry & DHW Gas Models
TO BE INSTALLED BY A TRAINED COMPETENT PERSON
Installation and Commissioning Instructions
THIS MANUAL IS TO BE LEFT WITH END USER

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Brandon Dry and is the answer not in the manual?

Questions and answers

Summary of Contents for Stanley Brandon Dry

  • Page 1 Brandon Dry & DHW Gas Models TO BE INSTALLED BY A TRAINED COMPETENT PERSON Installation and Commissioning Instructions THIS MANUAL IS TO BE LEFT WITH END USER...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PAGE NO. Introduction ............2 Specification .
  • Page 3: Introduction

    S.I. 101 of 1992 (as amended). S.I. 150 of 1995 (as amended). IMPORTANT NOTICE: Any alteration to this appliance that is not approved in writing by Waterford Stanley, will render the guarantee void. The complete installation must be done in accordance with the current Standards &...
  • Page 4: Specification

    IRELAND: ALL GAS APPLIANCES MUST BE U.K.: ALL GAS APPLIANCES MUST BY LAW BE INSTALLED BY A COMPETENT PERSON AS INSTALLED BY A COMPETENT PERSON, ONLY OUTLINED IN I.S. 813. USE A C.O.R.G.I REGISTERED ENGINEER. This appliance is hot while in operation and retains its heat for a long period of time after use. Children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
  • Page 5: Technical Data

    FEATURE METRIC (mm) IMPERIAL (inches) Hot Plate 550W x 323L W x 12 Roasting Oven 390W x 310H x 406D W x 12 H x 16D Simmering Oven: 390W x 220H x 406D W x 8 H x 16D This appliance has been tested and approved in accordance with the Gas Appliance Directive (90/396/EEC), the Low Voltage Directive (72/23/EEC) and the Electromagnetic Compatibility Directive (89/336/EEC) as amended.
  • Page 6: Schematic

    SCHEMATIC Fig 1. Left-hand Hotplate Cover. 150mm (6”) 90° Bend Bend Cleaning Plate Towel Rail Firedoor Burner Door Main Oven Door Simmer Oven Door 10. Base Frame 11. Hotplate 12. Simmer and Cleaning Plate 13. High Limit Reset Button 14. 6” (150mm) to 5” (125mm) Adaptor 15.
  • Page 7: Location

    LOCATION To isolate the appliance completely unplug from the mains socket. Always ensure that this socket is Prior to installation, ensure that the local distribution easily accessible and close to the appliance. conditions (nature of the gas and gas pressure) and Persons in charge of this appliance should be aware adjustment conditions are compatible.
  • Page 8: Reduced Clearances

    (See Figs. 7 & 8) Fig.4 The clearances for non-combustible materials can then be observed (see Fig.4) An optional hob filler strip can be fitted between the Stanley and adjacent units. Refer to fig.7. Fig.7 Fig.5 REDUCED CLEARANCES Fig.8...
  • Page 9: Pre-Installation Check

    unprotected mild steel or other material which is Fig.9 likely to corrode. Where flue piping passes through a closure plate with a sliding door, ensure that the pipe continues up and is ultimately connected to the flue liner and well sealed with fire cement. Do not connect to a chimney serving another appliance.
  • Page 10: Sealing

    Flue greater than 125mm Refer to Flue Assembly Instructions sheets. Fig.13) (5”) Diameter Fig.13 Fig. 12 The terminal position should be in accordance with B.S. 5440 Part 1 & the current Building Regulations. If it is necessary to offset the chimney the recommended angle is 60°...
  • Page 11: Suitable Materials

    250mm read the operating instructions. (10”) below the appliance connection. STANLEY CAST IRON PIPES AND BENDS ARE The combustion products will have a descaling HIGHLY RECOMMENDED FOR INTERIOR USE. effect on hardened soot deposits left from burning solid fuels.
  • Page 12: Ventilation And Combustion Air Requirements

    Part 4: Recommendation for installation burning appliances in operation at full rate. (i.e. design and installation. extraction fans, tumble dryers) with all external doors and windows closed. V E N T I L AT I O N A N D COMBUSTION REQUIREMENTS If spillage occurs following the above operation, an additional air vent of sufficient size to prevent this...
  • Page 13: Down Draughts

    Fig. 16 Fig. 18 Fig.17 DOWN DRAUGHTS However well designed, constructed positioned, the satisfactory performance of the flue can be adversely affected by down draught caused by nearby hills, adjacent tall buildings or trees. These can deflect wind to blow directly down the flue to create a zone of high pressure over the terminal.
  • Page 14: Meters (Natural Gas)

    METERS (NATURAL GAS) Step 1 A suitable gas meter must be connected to the Fit valve to the gas train pipe located at the bottom left side. (See Fig.20). service pipe either by a representative of the gas supplier or by an appointed contractor. If using an Step 2 existing meter have it checked to ensure that the Connect gas supply pipe to the valve.
  • Page 17: Domestic Hot Water System (Dhw Model Only)

    DOMESTIC HOT WATER SYSTEM 1.2 Non-Ferrous Materials (DHW MODEL ONLY) EN 29453: Soft Solder Alloys SYSTEM B.S. 864: Compression Tube Fittings The DHW Model must be connected to a fully B.S. 2871 & B.S. EN 1057 Copper and Copper pumped system. Alloys Care should be taken to ensure that the domestic DIRECT DOMESTIC CYLINDER...
  • Page 18: Pipe Thermostat

    6. Check that the oven thermostat is functional. NOTE: Copper cylinder should be “finned-coil” type with minimum capacity of 210 litres to B.S. 1566 & 7. Check that the gas supply is connected. B.S. 699. Cylinder thermostat set to 60 and connected to 8.
  • Page 19: Commissioning Of Burners

    19. Correct position of the air shutters should be Air Setting checked to give a CO reading of 8.2 - 9.4% The CO operating level for the burner is measured (NG) or 11.2 - 11.6% (LPG). at a test point using a combustion gas analyser (See Fig.27).
  • Page 20 Pressure Switch The control box checks that the COMMISSIONING TABLE: air pressure switch has switched by testing that continuity no NAT.GAS L.P.G. longer exists between pins 3 and Inlet Gas Pres. 20 mbar 37 mbar 6. If this is found to be Manifold Pres.
  • Page 21: Trouble Shooting

    Check wiring air pressure switch. (See Fig.31) Check air pressure switch by checking for phase on terminal 2 in the pressure switch. Waterford Stanley Bilberry, Waterford, Ireland. Telephone: (051) 302300 Facsimile: (051) 302375 Rev: 004 DP 020408...

This manual is also suitable for:

Brandon dhw

Table of Contents