Details Of Intake And Exhaust Piping Terminations; Direct Vent Roof Termination Kit; Field-Supplied Wall Termination Or Wall Ring Termination Kit - Lennox SLP98UHV SERIES Unit Information

Slp98uhv series
Hide thumbs Also See for SLP98UHV SERIES:
Table of Contents

Advertisement

Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged to outdoors.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In attic
or closet installations, vertical termination through the roof
is preferred. Figures 27 through 38 show typical termina-
tions.
1. Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the
side. Also, do not exit the intake on one side and the
exhaust on another side of the house or structure.
2. Intake and exhaust pipes should be placed as close to-
gether as possible at termination end (refer to illustra-
tions). Maximum separation is 3" (76mm) on roof ter-
minations and 6" (152mm) on side wall terminations.
3. On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
27).
4. Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip-
ing at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 24.
NOTE − Care must be taken to avoid recirculation of ex-
haust back into intake pipe.
3"(76mm) MAX.
Inches(mm)
8" (203mm) MIN
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)
FIGURE 27
SIZE TERMINATION
PIPE PER TABLE 24.
UNCONDITIONED
ATTIC SPACE
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
Page 47
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
* WALL
SUPPORT
C
See venting table 23 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust).
2" (51mm)
Vent Pipe
A−Minimum clearance
above grade or average
12" (508MM)
snow accumulation
B−Maximum horizontal
separation between
6" (152MM)
intake and exhaust
C−Minimum from
8" (203MM)
end of exhaust to
inlet of intake
D−Maximum exhaust
12" (305MM)
pipe length
E−Maximum wall support
distance from top of each
6" (152MM)
pipe (intake/exhaust)
FIGURE 28
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
SIZE TERMINATION
PER TABLE 24
D
B
STRAIGHT
APPPLICATION
D
B
A
EXTENDED
APPLICATION
3" (76mm)
Vent Pipe
12" (508MM)
6" (152MM)
8" (203MM)
20" (508MM)
6" (152MM)