Lennox EL195UHE Unit Information page 44

El195uhe series units
Table of Contents

Advertisement

E−Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com-
bustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
TABLE 18
Unit
All
The maximum carbon monoxide reading should not exceed 50 ppm.
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Natural to
LP/Propane
Unit
0 − 7500 ft
(0 − 2286m)
−045
−070
−090
*69W73
−110
−135
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).
CO
%
CO
%
2
For Nat
2
For LP
7.2 − 8.2
8.6 − 9.6
High Altitude
Natural Burner
Orifice Kit
7501 − 10,000 ft
(2286 − 3038m)
73W37
F−High Altitude
NOTE − In Canada, certification for installations at eleva-
tions over 4500 feet (1372 m) is the jurisdiction of local au-
thorities.
Units installed at altitude of 4501 − 10,000 feet (1373 to
3048 m) may require a pressure switch change which can
be ordered separately. Table 19 lists conversion kit and
pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory−set and re-
quires no adjustment.
TABLE 19
High Altitude
LP/Propane Burner
Orifice Kit
7501 − 10,000 ft
(2286 − 3038m)
*68W68
Page 44
High Altitude Pressure Switch
4501 − 7500 ft
7501 −10,000 ft
(1373 − 2286m)
(2286 − 3048m)
No Change
80W60
80W66
80W59
80W65
80W59
80W66
80W59
80W65
80W59