Lennox EL195UHE Unit Information page 38

El195uhe series units
Table of Contents

Advertisement

EL195UHE NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 14.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 47
Condensate Piping
This unit is designed for either right- or left-side exit of con-
densate piping in upflow applications. In horizontal applica-
tions, the condensate trap must extend below the unit. An
8" service clearance is required for the condensate trap.
Refer to figures 48 and 49 for condensate trap locations.
Figure 55 shows trap assembly using 1/2" PVC or 3/4"
PVC.
NOTE − If necessary the condensate trap may be installed
up to 5´ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of
PVC pipe required to reach available drain.
2 − Use a 3/8 allen wrench and remove plug (figure 48)
from the cold end header box at the appropriate loca-
tion on the side of the unit. Install field−provided 1/2
NPT male fitting into cold end header box. Use Teflon
tape or appropriate pipe dope.
3 − Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 55.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig-
ure 55. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope
from the furnace to the drain.
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
Page 38
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
(same on
right side)
1−1/2 in.
NOTE − In upflow applications where side return
air filter is installed on same side as the conden-
sate trap, filter rack must be installed beyond
condensate trap or trap must be re−located to
avoid interference.
FIGURE 48
5 − Figures 50 and 51 show the furnace and evaporator
coil using a separate drain. If necessary the conden-
sate line from the furnace and evaporator coil can
drain together. See figures 52, 53 and 54.
Upflow furnace (figure 53) − In upflow furnace applica-
tions the field provided vent must be a minimum 1" to a
maximum 2" length above the condensate drain outlet
connection. Any length above 2" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (figure 54) − In horizontal furnace
applications the field provided vent must be a mini-
mum 4" to a maximum 5" length above the condensate
drain outlet connection. Any length above 5" may re-
sult in a flooded heat exchanger if the combined pri-
mary drain line were to become restricted.
NOTE − In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE − Vinyl tubing may be used for condensate drain.
Tubing must be 1−1/4" OD X 1" ID and should be
attached to the drain on the trap using a hose clamp.
CAUTION
Do not use copper tubing or existing copper conden-
sate lines for drain line.
6 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start−Up section.
Plug
(same on left side)

Advertisement

Table of Contents
loading

Table of Contents