Adding Refrigerant - Samsung AQV09F Series Installation Manual

Split-type air conditioner
Hide thumbs Also See for AQV09F Series:
Table of Contents

Advertisement

C
I
OMPLETING THE
NSTALLATION
Purging the Connected Pipes(Continued)
Model
AQ09/12VBC
AQ09/12NSB
AQ09/12FC
AQ09/12NSA
18/24
Refrigerant type
R410A
 GWP=Global Warming Potential
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol.
Indoor unit
a
= (
) kg
+
= (
) kg
b
16
E-
08'FORTE_VIVACE_Inv_IM_28492A£¨4£©_E.indd 16

Adding Refrigerant

Add refrigerant charge according to table below:
A
 If you use a pipe...
0
15
Important information regulation regarding the
refrigerant used
GWP value
1975
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. Do not vent gases into the atmosphere.
Please fill in with indelible ink,
-
the factory refrigerant charge of the product,
-
the additional refrigerant amount charged in the field and
-
+
on the refrigerant charge label supplied with the product.
Note
d
Outdoor unit
= (
) kg
c
 The filled-out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop valve cover).
Charging the refrigerant under conditions of liquid by
using a liquid pipe
R410A is a mixed type of refrigerant. It is necessary for recharging under
conditions of liquid. When recharging refrigerant from the refrigerant cylinder
to the equipment, follow the instructions below.
Before recharging, check whether the cylinder has a siphon or not.
There are two ways to recharge the refrigerant.
Cylinder with siphon
Charge the refrigerant standing
the cylinder upright.
Note
longer than 5 meters,
shorter than 5 meters,
the total refrigerant charge.
a. Factory refrigerant charge of the product: see unit name plate
b. Additional refrigerant amount charged in the field
( Refer to the above information for the quantity of refrigerant
replenishment.)
c. Total refrigerant charge
d. Refrigerant cylinder and manifold for charging
siphon
 If R410A refrigerant is charged with gas, the composition of the
charged refrigerant changes and the characteristics of the
equipment vary.
 During the measuring operation of refrigerant quantity added use
an electronic balance. If cylinder doesn't have syphon, upset it.
Then...
'A'g of refrigerant R410A must
be added for each extra metre.
The purge time is normal.
Cylinder without siphon
Charge the refrigerant turning the
cylinder upside down.
2007-12-6 9:32:58