Procedure:
Shut the UPS down by pressing key '0' on the Operating panel.
Remove Mains voltage from the input socket.
Remove the Front Panel and disconnect the Battery plug.
Wait 10 Minutes to allow discharge of the DC-Capacitors.
Remove dangerous voltage and then remove the UPS cover, following instructions on page 5.
Measure the voltage across R316/R345* and R317/R346*. ( < 20 Volt )
*(For VH700-VH1500 measure voltage on resistor R345/R346, and for VH2000/VH3000 on R316/R317)
Modifications reserved