2. Outdoor unit thermistor temperature characteristics
Resistance
Connector
CN8
1
+
-
500K
Tester
400K
(K )
300K
Resistance at 25
52.76 k
200K
5.8K
3.06K
4.17K
2.28K
100K
0
-20
0
20
60
80
100
Temperature(
)
TH1 Compressor thermistor
Thermistor
No.
Compressor thermistor
TH1
Heat exchanger thermistor
TH2
Outdoor air temperature thermistor
TH3
Suction thermistor
TH4
2-way valve thermistor
TH5
Connector
CN8
10
1
40K
Tester
Resistance at 0
Resistance
(In case of TH2 heat exchanger thermistor)
30K
14.57 k
(K )
Resistance at 25
4.431 k
20K
TH2
TH5
10K
1.72K
0
120
-20
0
20
40
60
Temperature(
TH2 Heat exchanger thermistor
TH3 Outdoor air temperature thermistor
TH4 Suction thermistor
TH5 2-way valve thermistor
Connector
Color
Before measuring resistance,
No. (1) - No. (2)
Red
disconnect connectors from PWB.
No. (3) - No. (4)
Orange
No. (5) - No. (6)
Green
No. (7) - No. (8)
Black
No. (9) - No. (10)
Yellow
3 – 6