Legend - Daikin WRA Installation And Maintenance Data

Water to water source heat pumps 3 to 35 tons with r-410a
Table of Contents

Advertisement

Wiring Diagram

Legend

208-230/60/3, Unit Sizes 120, 150, 180, 240 and 300
LEGEND
FUNCTIONAL
LINE
DESIGNATION
NUMBER
C1L
44
OPTIONAL INDICATOR LIGHT - COMPRESSOR 1 ON
C2L
45
OPTIONAL INDICATOR LIGHT - COMPRESSOR 2 ON
CC1
27
COMPRESSOR NO. 1 CONTACTOR
CC1-A1
#
"CC1" AUXILIARY CONTACT NO. 1
CC1-A2
#
"CC1" AUXILIARY CONTACT NO. 2 (WHEN USED)
CC2
38
COMPRESSOR NO. 2 CONTACTOR
CC2-A
#
"CC" AUXILIARY CONTACT (WHEN USED)
CCH,CCH2
11,12
CRANKCASE HEATER NO. 1 & NO. 2
CCM1
21
COMPRESSOR CONTROL MODULE NO. 1
CCM2
32
COMPRESSOR CONTROL MODULE NO. 2
CHR
60
CHANGEOVER RELAY (WHEN USED)
CM1
2
COMPRESSOR NO. 1
CM2
5
COMPRESSOR NO. 2
CR1
58
COMPRESSOR NO. 1 PILOT RELAY
CR2
59
COMPRESSOR NO. 2 PILOT RELAY
EGB
4
EQUIPMENT GROUNDING BAR
EMR
67
OPTIONAL ENERGY MANAGEMENT RELAY
F1,F2,F3
7
FUSING - SEE FUSE TABLE
FL
43
OPTIONAL INDICATOR LIGHT - FAULT
FS-L
23
OPTIONAL FLOW PROVING SWITCH – LOAD COIL
FS-S
23
OPTIONAL FLOW PROVING SWITCH – SOURCE COIL
HDT1
24
HIGH DISCHARGE TEMPERATURE CUTOUT NO. 1
HDT2
35
HIGH DISCHARGE TEMPERATURE CUTOUT NO. 2
HP1
25
HIGH DISCHARGE PRESSURE CUTOUT SWITCH NO. 1
HP2
36
HIGH DISCHARGE PRESSURE CUTOUT SWITCH NO. 2
LP1
25
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 1 (CKT 1)
LP2
36
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 2 (CKT 2)
LP3
21
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 3 (CKT 1)
LP4
32
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 4 (CKT 2)
LTC
17,25,36 LOW FLUID TEMPERATURE CUTOUT MODULE
PDB
1,2,3
POWER DISTRIBUTION BLOCK
PM
9,51
OPTIONAL POWER MONITOR
RVS1
52
REVERSING VALVE SOLENOID CKT 1 (WHEN USED)
RVS2
53
REVERSING VALVE SOLENOID CKT 2 (WHEN USED)
TB1
+
TERMINAL BOARD NO. 1
TB2
64,65
TERMINAL BOARD NO. 2
TB3
+
TERMINAL BOARD NO. 3
TB4
21
TERMINAL BOARD NO. 4
TB5
32
TERMINAL BOARD NO. 5
TB6
11
TERMINAL BOARD NO. 6
TB7
67,68
TERMINAL BOARD NO. 7 (WHEN USED)
TR1
50
CONTROL TRANSFORMER NO. 1
TR2
15
CONTROL TRANSFORMER NO. 2
TC
54,54
TEMPERATURE CONTROLLER (OPTIONAL)
TS-C
55
AQUASTAT – COOLING (WHEN USED)
TS-H
54
AQUASTAT – HEATING (WHEN USED)
# SEE LINE NUMBER TO THE RIGHT OF CONTACTOR COIL ON WIRING DIAGRAM.
+ MULTIPLE LINE NUMBERS.
FUSE TABLE
FUSE NO.
CLASS
VOLTS AC
F1,F2,F3†
CC
600
† F3 IS USED ONLY WHEN OPTIONAL POWER MONITOR IS FURNISHED.
+ 208/230 VOLT UNITS USE 2 AMPERES.
460 VOLT UNITS USE 1 AMPERES.
1
THREE PHASE FIELD POWER SUPPLY PER UNIT RATING PLATE. MINIMUM CIRCUIT
AMPACITY AND MAXIMUM SIZE OF TIME-DELAY FUSE OR HACR-TYPE CIRCUIT BREAKER
PER UNIT RATING PLATE. PROVIDE DISCONNECTING MEANS AND EQUIPMENT
GROUNDING AS REQUIRED.
2
TRANSFORMER MAY HAVE TAPS FOR MULTIPLE SYSTEM POWER SUPPLY VOLTAGES.
BEFORE APPLYING POWER TO THE UNIT, ENSURE TRANSFORMER IS WIRED FOR
APPROPRIATE SYSTEM POWER SUPPLY. INSULATE SEPARATELY ANY UNUSED LEADS.
POLARITY IS NOT INDICATED. TYPICAL TRANSFORMER SHOWN. SEE TRANSFORMER LABEL
FOR LEAD COLOR CODING. A PUSH TO RESET FUSEHOLDER-TYPE THERMAL CIRCUIT
BREAKER IS MOUNTED ON THE TRANSFORMER. THE CIRCUIT BREAKER IS WIRED IN SERIES
WITH ONE SIDE OF THE TRANSFORMER SECONDARY WINDING.
3
SEE FIGURE 1 ON SHEET 3 OF THIS DRAWING FOR BOARD LAYOUT, SENSOR
LOCATIONS, TEMPERATURE SETTING NOTE, AND SENSOR RESISTANCE VERSUS
TEMPERATURE GRAPH.
SEE FIGURE 2 ON SHEET 3 OF THIS DRAWING FOR COMPRESSOR CONTROL MODULE
4
OPERATION.
5
WHEN "FS-L" AND "FS-S" ARE NOT USED, THIS WIRE CONNECTS DIRECTLY TO
TERMINAL 5 OF "TB3".
WIRED AS SHOWN FOR OPEN LOOP OR HIGH TEMPERATURE CLOSED LOOP
6
APPLICATIONS. FOR LOW TEMPERATURE CLOSED LOOP APPLICATIONS, MOVE THIS
WIRE FROM TERMINAL 6 TO TERMINAL 7 ON "TB4".
7
WHEN "LTC" IS NOT USED, THIS WIRE CONNECTS DIRECTLY FROM "HPS1" TO EITHER
"HDT1" WHEN USED OR TO HPS TERMINAL OF "CCM1" ("HDT1" NOT USED).
8
WHEN OPTIONAL "LTC" IS NOT USED, THESE TWO WIRES ARE SPLICED TOGETHER.
9
WIRED AS SHOWN FOR OPEN LOOP OR HIGH TEMPERATURE CLOSED LOOP
APPLICATIONS. FOR LOW TEMPERATURE CLOSED LOOP APPLICATIONS, MOVE THIS
WIRE FROM TERMINAL 8 TO TERMINAL 9 ON "TB5".
10
WHEN "LTC" IS NOT USED, THIS WIRE CONNECTS DIRECTLY FROM "HPS2" TO EITHER
"HDT2" WHEN USED OR TO HPS TERMINAL OF "CCM2" ("HDT2" NOT USED).
11 WHEN OPTIONAL "LTC" IS NOT USED, THESE TWO WIRES ARE SPLICED TOGETHER.
12
WHEN "CHR" IS NOT USED, THIS WIRE CONNECTS DIRECTLY TO TERMINAL 1 ON "PM" --
OR-- WHEN "PM" IS NOT USED, TO TERMINAL 4 ON "EMR" --OR-- WHEN "EMR" IS NOT
USED,TO TERMINAL R ON "TB1".
13
IF POWER MONITOR OUTPUT CONTACTS DO NOT TRANSFER WHEN POWER IS APPLIED
TO UNIT (BICOLOR LED GLOWS GREEN UNDER NORMAL CONDITIONS AND RED
DURING FAULT CONDITIONS):
1.
VERIFY THAT ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT
VOLTAGE. IF ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT VOLTAGE,
PHASE ROTATION MAY BE INCORRECT. PERFORM STEP 2.
2.
DISCONNECT POWER TO THE WW* UNIT. VERIFY THAT POWER IS IN FACT
DISCONNECTED. SWAP ANY TWO OF THE THREE UNIT POWER SUPPLY WIRES. WHEN
POWER IS REAPPLIED, OUTPUT CONTACTS SHOULD NOW TRANSFER.
Page 24 of 44
DESCRIPTION
AMPERES
TIME DELAY
+
YES
Water to Water Source Heat Pumps
WIRE COLOR LEGEND
BK:
BLACK
PK:
BL:
BLUE
PR (V): PURPLE (VIOLET)
BR: BROWN
R:
G:
GREEN
W:
GY: GRAY
Y:
O:
ORANGE
NOTES:
NUMBER PLACED AFTER DASH FOLLOWING COLOR
CODE INDICATES WIRE GAGE. FOR EXAMPLE> BK-12 IS
A BLACK, 12 AWG WIRE.
NO NUMBER AFTER COLOR CODE INDICATES 18 AWG
WIRE. FOR EXAMPLE> BK IS A BLACK 18 AWG WIRE.
WHEN COLOR COMBINATIONS ARE USED, THE COLORS
ARE SEPARATED BY A SLASH (/). FOR EXAMPLE:
ORANGE/WHITE (O/W). THE PRIMARY COLOR CODE OF
THE WIRE IS SHOWN FIRST, TRACER OR STRIPE SHOWN
LAST.
BONDING CONDUCTORS INDICATED AS GREEN MAY
ALSO BE GREEN WITH ONE OR MORE YELLOW STRIPES.
SYMBOL LEGEND
FACTORY WIRING
OPTIONAL FACTORY WIRING
FIELD WIRING
OPTIONAL FIELD WIRING
EARTH GROUND
CHASSIS (PANEL) GROUND
TERMINAL BOARD NO. 1 (TB1)
TERMINAL BOARD NO. 2 (TB2)
TERMINAL BOARD NO. 3 (TB3)
TERMINAL BOARD NO. 4 (TB4)
TERMINAL BOARD NO. 5 (TB5)
TERMINAL BOARD NO. 6 (TB6)
TERMINAL BOARD NO. 7 (TB7)
COIL
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
IDENTIFIABLE TERMINAL
NON-IDENTIFIABLE TERMINAL,
OTHER WIRE JUNCTIONS,
INCLUDING SCHEMATIC
14
TYPICAL FIELD CONTROL WIRING SHOWN. ACTUAL FIELD WIRING MAY DIFFER FROM
WIRING SHOWN HERE. USE 18 AWG MINIMUM FOR FIELD 24 VOLT CONTROL WIRING.
TYPICAL REMOTE SWITCH SHOWN. REMOTE SWITCH MAY BE SUPPLIED BY OTHERS
OR IS AVAILABLE AS AN OPTIONAL ACCESSORY FROM THE FACTORY. MINIMUM PILOT
DUTY RATING OF EACH POLE OF REMOTE SWITCH IS 24 VOLT-AMPERES @ 24 VOLTS
AC WHEN CONNECTED AS SHOWN.
15
"RVS1" AND "RVS2" ARE USED ONLY WITH WWR MODELS AND ARE ENERGIZED IN
COOLING MODE.
"RVS1" AND "RVS2" ARE NOT USED WITH WWC AND WWH MODELS.
16
AQUASTATS "TS-H" AND "TS-C" ARE NOT USED WHEN OPTIONAL FACTORY INSTALLED
TEMPERATURE CONTROLLER "TC" IS FURNISHED. TYPICAL AQUASTATS SHOWN.
AQUASTATS MAY BE SUPPLIED BY OTHERS OR ARE AVAILABLE AS AN OPTIONAL
ACCESSORY FROM THE FACTORY. MINIMUM PILOT DUTY RATING OF EACH POLE OF
AQUASTAT IS 24 VOLT-AMPERES @ 24 VOLTS AC WHEN CONNECTED AS SHOWN.
17
THIS WIRE CONNECTS DIRECTLY FROM TERMINAL S1 TO TERMINAL Y1 ON "TB1" WHEN
OPTIONAL TEMPERATURE CONTROLLER "TC" IS NOT FURNISHED.
18
THIS WIRE CONNECTS DIRECTLY FROM TERMINAL S2 TO TERMINAL Y2 ON "TB1" WHEN
OPTIONAL TEMPERATURE CONTROLLER "TC" IS NOT FURNISHED.
WHEN OPTIONAL TEMPERATURE CONTROLLER "TC" IS FURNISHED, INSTALLER MUST
19
PROGRAM CONTROLLER. REFER TO TEMPERATURE CONTROL INSTALLATION
INSTRUCTIONS.
WITH REVERSE-CYCLE WWR UNITS, PROGRAM CONTROLLER AS ONE STAGE
COOLING AND ONE STAGE HEATING. STAGE 1 IS THE COOLING STAGE AND STAGE 2 IS
THE HEATING STAGE.
INSTALL SENSOR ON THE WATER INLET PIPE (LOAD COIL).
20
CONDUCTOR "O" REQUIRED WITH WWR REVERSE CYCLE UNITS.
CONDUCTOR "O" NOT USED WITH WWC COOLING AND WWR HEATING UNITS.
21
"CHR" IS USED ONLY WITH "WWR" UNITS.
"CHR" IS NOT USED WITH "WWC" AND "WWH" UNITS.
22
COMPRESSOR RELAY CONTACTS ARE PROVIDED TO OPERATE AN EXTERNAL PILOT
DUTY LOAD (SUCH AS A PUMP RELAY COIL) WITH THE COMPRESSORS.
AN EXTERNAL LOAD POWERED BY TRANSFORMER "TR1" IN THE WW* UNIT MUST
NOT EXCEED 12 VA SEALED (96 VA INRUSH) @ 24 VOLTS AC.
EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO
CLASS 2 CIRCUITS ONLY (30 VOLTS AC MAXIMUM). EXTERNAL LOAD
CHARACTERISTICS MUST NOT EXCEED 10 AMPS MAKE, 1 AMP BREAK. MAINTAIN
SEPARATION BETWEEN CLASS 2 CIRCUITS OF DIFFERENT SOURCES.
PROVIDE DISCONNECTING MEANS, EQUIPMENT GROUNDING, AND
OVERCURRENT PROTECTION AS REQUIRED.
WIRING DIAGRAM # 0962I-2633B, REV. B
WW* 120, 150, 180, 240, 300
PINK
RED
WHITE
YELLOW
IM 1072-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents