MODEL DESCRIPTION
WW
-
-
A = 24 HOUR TIMER
B = 7 DAY TIMER
1 = 1 WASH SEQUENCE
2 = 2 WASH SEQUENCES
3 = 3 WASH SEQUENCES
4 = 4 WASH SEQUENCES
5 = 5 WASH SEQUENCES
7 = 3/4" PIPE
10 = 1" PIPE
WATER REQUIREMENTS
WATER TEMPERATURE 140° F. TO 180° F
WATER PRESSURE = 40 PSI TO 60 PSI
AVE. WATER USAGE = 1.1 GPM PER LN. FT. OF HOOD
3.50
3.50
18.91
HINGED
DOOR
OPTIONAL
VACUUM BREAKER
FIELD INSTALLED
PIPE BY OTHERS
UNION
WATER TEMPERATURE
& PRESSURE GAUGE
DETERGENT PUMP
SOLENOID VALVE
SHOCK ARRESTOR
GATE VALVE
UNION
PIPE BY OTHERS
WATER INLET
April 2005
WATER WASH CONTROL PANEL - MODEL WW
W / VACUUM BREAKER
PIPE SIZE
3/4"
1"
HOOD LENGTH > 20' MUST USE THE SEQUENCE
WASH OPTION. PIPE SIZE WILL DEPEND ON THE
LONGEST LENGTH OF HOOD WASHED AT ONE TIME
(@ 40 PSI)
12.56
8.37
ELECTRICAL
CONNECTIONS
PIPE CONNECTION
(.88 DIA. HLS)
(1.75 DIA. HOLE)
TO HOOD(S)
CHECK VALVE
FIELD INSTALLED
1"
DETERGENT TANK
2.5 GAL. CAPACITY
®
PIPE SIZE
LENGTH OF LONGEST HOOD
OR SEQUENCE OF HOOD
4' - 10'
>10' - 20'
SEQUENCE OF OPERATIONS
15 SEC. COLD WATER PURGE (OPTIONAL 30 SEC.)
4 MIN. WASH (OPTIONAL 0 TO 10 MIN.)
30 SEC. DETERGENT PURGE (OPTIONAL 1 MIN.)
15 MIN. SEQUENCE DELAY (OPT. 0 TO 45 MIN.)
1 MIN. DRAIN DOWN (OPTIONAL 10 MIN.)
1 MIN. DRY (FANS ON) (OPTIONAL 10 MIN.)
6.37
4.37
2.37
2.00
9.53
HINGED
DOOR
6.0
DETAIL OF LABEL & SWITCHES
WATER WASH HOOD CONTROL PANEL
HOOD LIGHTS
1. PUSH THE START FAN SWITCH BEFORE TURNING ON THE COOKING EQUIPMENT.
2. WHEN THE COOKING EQUIPMENT HAS BEEN SHUT DOWN AND ALLOWED TO
COOL PROPERLY, PUSH THE STOP FAN / START WASH SWITCH. THIS WILL
TURN OFF THE FANS AND START THE WASH CYCLE. IF THE SYSTEM HAS
THE 24 HOUR TIMER OPTION THE WASH CYCLE WILL BEGIN AT THE SET
TIME. AFTER THE WASH CYCLE THE SYSTEM WILL RESET FOR THE NEXT
OPERATION.
SUPPRESSION SYSTEM. IN FIRE MODE THE WATER WASH SYSTEM WILL TURN
ON THE EXHAUST FAN AND CONTINUOUSLY SPRAY WATER INTO THE HOOD.
OPTIONAL:
LOW DETERGENT INDICATOR
SEQUENCED HOODS
TIMER
24 HOUR
7 DAY
30"
9"
KITCHEN VENTILATION SYSTEMS
LOW DETERGENT
FIRE MODE
OPTIONAL
INDICATOR
INDICATOR
LIGHT
LIGHT
STOP FAN /
START WASH
START FAN
LIGHTED
LIGHTED
LIGHTED
PUSH-
PUSH-
PUSH-
BUTTON
BUTTON
BUTTON
SWITCH
SWITCH
SWITCH
OPERATING INSTRUCTIONS
FIRE MODE
FIRE MODE IS INITIATED BY AN EXTERNAL SIGNAL FROM A FIRE
SEE THE INSTALLATION AND OPERATION MANUAL FOR MORE INFORMATION.
30"
P.N. 454034
39