Solid Pack With Metal Supports; Masonry Chimney - Quadra-Fire 2100 Millennium Owner's Manual

Advanced combustion technology (act) wood stove
Hide thumbs Also See for 2100 Millennium:
Table of Contents

Advertisement

R
SOLID PACK CHIMNEY WITH METAL SUPPORTS AS A THIMBLE
For the method of installation to a masonry chimney shown in Figures 12A & 12B on page 12, it will be necessary to
purchase a 12" (305mm) long 8" (203mm) inside diameter, section of prefabricated listed solid pack chimney to use as a
thimble. Purchase a wall spacer, trim collar, and a wall band manufactured to fit the chimney section you purchase.
The safety features of this system are twofold: 1) A 2" (51 mm) air space between the chimney section and combustible
wall; and, 2) The 1" (25mm) air space around the chimney connector as it passes through the chimney section to
the chimney.
The location of the opening through the wall to the chimney must leave a minimum 18" (457mm) vertical clearance
between the connector pipe and the ceiling (or minimum recommended from pipe manufacturer) to prevent the
ceiling from catching fire.
Measure for the center-line as shown in Figure 10A below. Cut an opening in the wall large enough to accommodate the
outside dimension of the chimney section plus the minimum air space specified by its manufacturer. It may be necessary
to cut the wall studs and install a header and a sill frame to maintain the wall support. The hole in the chimney must have
at least an 8" (203mm) diameter fire clay liner or equivalent, secured with refractory mortar. If it is necessary to cut a hole
in the chimney liner, use extreme care to keep it from shattering.
FIGURE 10A
Wall
Opening
Center Line
Add center-line measurement to
depth measurement of your floor
protector. Mark this combined mea-
surement at correct wall location
for your installation, maintaining
minimum clearance to combustibles,
and mark wall for a 10" x 10" (254mm
x 254mm) square hole.
WARNING! ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER'S INSTRUCTIONS FOR PROPER INSTALLATION.
CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING OR WALL, NEVER
PASSING THROUGH A COMBUSTIBLE CEILING OR WALL. THE CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR
ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, OR A FLOOR, OR CEILING. MAINTAIN MINIMUM CLEARANCES
TO COMBUSTIBLES AS REFERENCED ON PAGE 6.
Page 10
2100 ACT Millennium Wood Stove
FIGURE 10B
1" (25mm) CLEARANCE
Center of Hole
WITH FIRESTOP
Center Line
FLOOR
PROTECTOR
CONCRETE CAP
RAFTER
CEILING
JOIST
COMBUSTIBLE
THIMBLE,
12" (305mm)
OF BRICK
FIRECLAY FLUE
LINER WITH AIR
SPACE
FLASHING
EAVE
1" (25mm)
CLEARANCE
SHEATHING
AIRTIGHT
CLEANOUT DOOR
250-6931C November 3, 2004