Annual Maintenance And Inspection - Slant/Fin CHS-85 Installation And Operating Instructions Manual

Chs series high efficiency fire tube condensing gas boiler
Hide thumbs Also See for CHS-85:
Table of Contents

Advertisement

Slant Fin Corp.
│ Installation and Operation Instructions

14.0 ANNUAL MAINTENANCE AND INSPECTION

This unit must be inspected at the beginning of every heating season by a Qualified Technician.
Annual Inspection Checklist
 1. Lighting is smooth and consistent, and the combustion fan is noise & vibration free.
 2. The condensate drain freely flows, and is cleaned of sediment.
 3. Relief Valve and air vents are not weeping.
 4. Low water cut off is tested (remove and clean a minimum of once every 5 years, see Section 10.0)
 5. Examine all venting for evidence of leaks. Ensure vent screens are cleaned and clear of debris.
 6. Check the burner plate for signs of leaking.
 7. The combustion chamber must be inspected and if necessary cleaned.
 8. Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and
liquids.
 9. Ensure there is nothing obstructing the flow of combustion and ventilation air.
 10. Listen for water flow noises indicating a drop in boiler water flow rate.
Important - The hydronic system may need to be flushed to eliminate hard water scale
(Use Fernox DS-40 Descaler, Slant/Fin PN: 81 8182 000).
 11. Verify proper operation after servicing.
Wiring Labels - Label all wires prior to disconnection when servicing controls. Wiring
errors can cause improper and dangerous operation.
Cleansers and Potable Water - Boiler system cleansers and corrosion inhibitors must not
be used to flush contaminants from water heaters or potable water systems.
Combustion Chamber Cleaning Procedure
Slant/Fin recommends having the combustion chamber cleaned after the first year of operation, with subsequent
cleanings scheduled based on the condition of the combustion chamber at the time. Units operating with LP Gas
or in an industrial environment may require more frequent cleanings.
Crystalline Silica - Read carefully the warnings and handling instructions pertaining to
Refractory Ceramic Fibers before commencing any service work in the combustion
chamber. Take all necessary precautions and use recommended personal protective equipment as required.
Cleaning Checklist
 1. Remove the demand for heat, allow the post-purge cycle to finish, turn gas and power supply off.
 2. Working inside the cabinet, disconnect the cabling to the combustion blower, gas valve, spark igniter
and flame sensor, then remove the air-inlet piping and Gas Valve/Venturi assembly (gas line is
disconnected at the factory supplied union fitting).
 3. Once the combustion chamber has cooled, remove the combustion blower followed by the burner plate –
be careful not to damage the insulation disc located underneath the burner plate.
 4. Use a vacuum with a high efficiency filter to remove any loose debris or dust.
 5. Remove the condensate trap from the bottom of the boiler and place a drain under the boiler condensate
drain.
 6. Wet the inside of the combustion chamber with warm water (do not use any chemicals). Use a garden
hose with a trigger nozzle to direct pressurized water through the heat exchanger tubes; the water will
exit via the condensate drain on the bottom. Continue process until the tubes are clear and the water
runs clean. Use dry rags or plastic to protect electrical components from being damaged by dripping or
spraying water.
 7. Disassemble the condensate trap and thoroughly clean it; then reassemble and securely connect it to the
boiler condensate drain, see Section 6.0.
 8. Remove the burner from the burner plate; clean if necessary using compressed air. Reattach the burner;
ensure the gasket is in perfect condition and is reinstalled (replace if necessary).
 9. Inspect the insulation disc located on the under-side of the burner plate. Replace if damaged.
 10. Re-install the burner plate; be sure the insulation disc is properly aligned.
components in the opposite order they were removed.
 11. Perform the Start-up and Operational Checklist detailed in the previous section.
Replace any gaskets or insulation discs that show any signs of damage and do not re-use.
Failure to follow these instructions may result in fire, property damage or death.
60
CHS Series
Reinstall remaining

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Chs-155Chs-110Chs-250Chs-300Chs-399Chs-175 ... Show all

Table of Contents