Condensate Drain - Slant/Fin CHS-85 Installation And Operating Instructions Manual

Chs series high efficiency fire tube condensing gas boiler
Hide thumbs Also See for CHS-85:
Table of Contents

Advertisement

Slant Fin Corp.
│ Installation and Operation Instructions

6.0 CONDENSATE DRAIN

This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion.
Steps must be taken to ensure condensate does not collect in the venting system; therefore, all exhaust piping
must slope back to the boiler a minimum 1/4" per linear foot of vent. Condensate must be drained from the unit
into a household drain.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the State of Massachusetts the
condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain
system (See Condensate Trap Installation Instructions for further details):
 DO NOT install condensate lines outside. A frozen or blocked drain will cause the condensate to back-up
and leak. This may result in damage to boiler components resulting in a no heat condition; property damage
may also occur.
 NEVER use copper, steel, or galvanized piping in the construction of the condensate system (condensate is
very corrosive and will corrode most metals).
 When a condensate pump is used or required, select a pump that is designed for residential furnaces.
Condensate Trap Installation Instructions (see Figure 6-1)
(Note: the Condensate Trap is factory supplied with the boiler and must be field installed)
1. Remove Hose-barb Adapter – Remove the Inlet Retaining Nut to access the Hose-barb Adapter (the
Hose-barb Adapter is not used and can be discarded).
2. Attach Corrugated Outlet Tube – Remove the Outlet Retaining Nut and Outlet Gasket and slide
components onto the Corrugated Outlet Tube – note orientation (gasket should be positioned
approximately 1/8" from the edge of the outlet tube – see Figure 6-1). Press the Corrugated Outlet Tube
into the Condensate Trap Outlet and firmly hand-tighten the Outlet Retaining Nut.
3. Attach to Boiler Condensate Drain (A) – Place the Inlet Retaining Nut and Inlet Gasket on the Boiler
Condensate Drain (gasket should be positioned approximately 5/8" from the edge of the Condensate
Drain Fitting – see Figure 6-1)
4. Attach to Boiler Condensate Drain (B) – Slide the Condensate Trap into place over the boiler
Condensate Drain Fitting – push-up until it bottoms out (ensure the Ball-float is placed inside the trap –
see Figure 6-1). Firmly hand-tighten the Inlet Retaining Nut.
5. Outlet to Drain – Route the condensate from the Corrugated Outlet Tube to a household drain, condensate
pump or neutralizer (check with your local authority regarding the disposal of condensate).
Carefully follow the above instructions and the accompanying figure – check to ensure
the condensate trap is secure to the bottom of the boiler and that no strain is placed on it.
Failure to install the condensate trap properly will result in flue gas spillage and leeching of carbon monoxide
emissions into the surroundings resulting in serious injury or death.
28
CHS Series

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Chs-155Chs-110Chs-250Chs-300Chs-399Chs-175 ... Show all

Table of Contents