G. Inspect the Venting System
The fireplace venting system is designed and constructed to
develop a positive flow adequate to remove flue gases to the
outside atmosphere. See fireplace installation instructions.
A spillage test must be made before the installed
appliance is left with the consumer
Close all doors and windows in the home.
Light the log set.
After three minutes, test with a smoke match, smoke
candle, stick incense or cigarette one inch below the top of
the opening (lintel) moving across the full width. If spillage
(smoke drawn into the room) occurs, it will most likely be
near the top, outside corners.
Possible Cures if Spilling Occurs
The damper should be fully open.
The fireplace opening needs to be reduced by adding a
drop panel across the top under the lintel.
The air supply from outdoors needs to be increased. Open
the outside air kit if the appliance is so equipped, or crack
open a door or window.
If necessary, seek expert advice. Do not operate this
appliance.
Cleaning
Periodic examination and cleaning of the venting system
of the fireplace should be done before initial use and at
least annually by a qualified agency.
WARNING
Fire Risk
Explosion Risk
Inspect external vent cap regularly.
Ensure no debris blocks cap.
Combustible materials blocking cap may
ignite.
Restricted air flow affects burner
operation.