Improper installation, adjustment, alteration, service or maintenance can cause
1.
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the latest revision of the National Fuel
Gas Code, ANSI Z223. (Available from the American Gas
Association, 8501 E. Pleasant Valley Road, Cleveland,
Ohio 44134). Reference should also be made to local gas
utility regulations and other codes in effect in the area
in which the installation is to be made. When installed
in Canada: The latest revision of the CAN1-B149.1 and/
or B149.2 Installation Codes for Gas-Burning Equipment
and/or local codes.
2.
Where required by the authority having jurisdiction, the
installation must conform to American Society of Me-
chanical Engineers Safety Code for Controls and Safety
Devices For Automatically Fired Boilers, ANSI/ASME
No.CSD-1.
3.
This boiler series is classified as a Category 1 and the
vent installation shall be in accordance with Part 7 of the
National Fuel Gas Code noted above when installed in
the United States. In Canada refer to the CAN1-B149.1
and or B149.2 Installation Codes for Gas-Burning Equip-
ment. Also refer to applicable provisions of the local build-
ing codes.
4.
This boiler has met safe lighting and other performance
criteria with the gas manifold and control assembly on the
boiler per the latest revision of ANSI Z21.13/CGA 4.9.
5.
The boiler shall be installed such that the gas ignition
system components are protected from water (drip-
ping, spraying, rain, etc.) during appliance operation and
service, (circulator replacement, condensate trap, control
replacement, etc.).
6.
Locate boiler on level, solid base as near the chimney
as possible and centrally located with respect to the heat
distribution system as practical.
7.
Allow 24 inches at the front and right side for servicing
and cleaning.
8.
When installed in a utility room, the door should be wide
enough to allow the largest boiler part to enter, or to
permit replacement of another appliance such as a water
heater.

INSTALLATION PROCEDURE

!
WARNING
injury or property damage.
9.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible flooring
special base must be used. (See Replacement Parts Sec-
tion.) The boiler can not be installed on carpeting. Mini-
mum clearances to combustible construction are:
TOP ........................................................... 18 IN.
FRONT ...............................................ALCOVE *
FLUE CONNECTOR ................................... 6 IN.
REAR ........................................................... 4 IN.
CONTROL SIDE .......................................... 9 IN.
OTHER SIDE ............................................... 3 IN.
NOTE: Greater clearances for access should supersede
* The definition of an Alcove is a three sided space with no
wall in front of the boiler. The ANSI standard for an alcove is
18 inches from the front of an appliance to the leading edge of
the side walls as shown below.
Minimum Clearances to Combustible Construction (as
4
fire protection clearances.
seen from above)
4"
3"
9"
BOILER
18"