Procedures And Conditions - State Water Heaters Standard Residential Gas Water Heater Service Handbook

Hide thumbs Also See for Standard Residential Gas Water Heater:
Table of Contents

Advertisement

RESIDENTIAL GAS, NON POWER VENTED, WATER HEATER
Residential Gas - continued
Sooting causes
:
If ...
the burner is clean but the chamber and/or flue
are sooted
the main burner, chamber and flue are sooted
Electrical Testing
This type of water heater has its own electrical
generating system.
When two dissimilar metals are joined together
and this joint is heated, a small, electrical current
will be produced. A thermocouple uses this
science.
Thermocouple output test
Procedures/Conditions:
Meter set for DC millivolt testing
Test from lower ECO (emergency cut off or energy cut off) solder joint to ground.
Note: If pilot will not stay lit, manually hold the top knob down in the pilot position. This allows
gas to flow to the pilot. Light the pilot and continue to hold this knob down while conducting the
test.
If ...
reading test of at least 13 mV is not present
reading test of at least 13 mV is present
State Water Heater
© 2004
SERVICE HANDBOOK
... then
check for lack of supply air.
check the following:
incorrect orifice
excessive gas pressure
loose main burner
cross threaded orifice
gas control valve gas seepage
loose gas connection in burner assembly.
... then
check that flame contacts end of
thermocouple
replace thermocouple.
continue to next test.
12
TO GROUND
Technical Training Department
Ashland city, TN