Inverter Settings
When setting the inverter communication parameters it is important to reset
the power afterwards so that the settings are saved to the inverter.
The parameters shown in the following table must be set using the PU
(Parameter Unit).
Note: Do not change these parameters, even though it is possible to monitor
them through the GOT. If they are changed, communication with the GOT is
disabled.
Setting item
Communication Station
number
Communication Speed
Stop bit length
Parity check presence/
absence
Number of
Communication retries
Communication check
time interval
Wait time setting
CR/LF selection
Protocol selection
Operation mode
selection
Communication startup
mode selection
EEPROM write
selection
Station Setting
Set each station number while making sure that each station number is used
only once. The station number can be set regardless of the cable connection
order. Station numbers do not have to be consecutive. The setting of the
Station number has to be between 0-31.
Indirect specification
Note: This document is for reference only. For detailed settings and safety information refer to the respective product manual.
Parameter
Set Value
Pr.117
0-31
Pr.118
192
Pr.119
10
Pr.120
1
Pr.121
9999
Pr.122
9999
Pr.123
0
Pr.124
1
Pr.549
0
Pr.79
0
Pr.340
1
Pr.342
0
8
Setting Contents
See following section
19200bps
Data length: 7bit
Stop bit length: 1bit
Odd
The inverter will not
come to an alarm stop.
Communication check
Suspension
0ms
With CR, without LF
Mitsubishi inverter
protocol
PU operation mode
Network operation mode
Written to RAM and
EEPROM