Reversing valve defrost
Longer than the defrost
15' or more
inhibit period
fan speed
30
30
set to
START/STOP switch
"HI"
Defrost signal
Preheating cancel
Preheating cancel
Preheating judgment
Preheati n g
HI
MED
Indoor
LOW
unit
SILENT
10
Super-LOW
Outdoor unit
HI or LO
HI or LO
Operation lamp
1
Latch-type
reversing valve
13
30
Reverse cycle
Deceleration
period
period
Up to 20'
Up to 3'
60
TDF412
TDF411
TDF413 TDF421
WMAX
DFMAX
3200
2700
2000
STARCPL
STARC PH
SGMNRP
Notes:
(1) During the defrost inhibit period, the product will be set as shown in the figure
below. Once the defrost is over, the product will set a new inhibit period based on
the external temperature at the time of compressor startup and, in the meantime,
will not accept defrost signals.
(2) If there is a big difference between the room temperature and the temperature
setting when the defrost comes to an end, the product can maintain its maximum
compressor speed (WMAX) or (WMAX2) for up to 120 minutes.
(3) The defrost period lasts up to DFMXTM (20 minutes).
(4) After the product stops running during defrost, it will switch to auto-fresh defrost.
(5) Auto-fresh defrost is not conducted within 15 minutes after operation startup or
within 15 minutes after the end of the defrost.
(6) The Super-LOW fan operation during reservation or during preheating after
defrost will be stopped at a heat exchanger temperature of 16
Setting a defrost inhibit period
Time
Notes:
(1) The first inhibit time after operation startup is set to DFTIM_FST.
(2) For the second and subsequent times, the inhibit time is set according to
the time required for a reverse cycle.
If the reverse cycle operation time [DEFCOL], set DFTIM_COL.
If the reverse cycle operation time [DEFCOL], set a time according to the
external temperature by referring to the above figure.
Auto-fresh defrost
Stop
Sleep key
15
Operation
lamp
Remote control
"SLEEP" lit
Timer lamp lit
HI
Indoor
MED
Reverse cycle
unit
period
LOW
Up to 20'
3
SILENT
See "Basic mode."
Sleep
1
See "Basic mode."
4000
Outdoor unit
STARCPL
STARC PH
Upper and
Shut
lower louvers
Horizontal
Facing downwards
Notes:
(1) Pressing the "sleep key" will start the night operation.
(2) Setting the sleep key will limit the compressor's maximum speed to WSZMAX and the indoor unit to
"sleep LOW" (FCSOY).
or less.
(3) If operation modes are changed during sleep operation, the product will switch to the operation
mode from the time of the change onwards and start the sleep control.
(4) Changing the fan speed mode will not change the indoor unit speed ("sleep LOW").
(5) Entering defrost during a sleep operation will initiate the defrost and switch back to the sleep
operation at the end of the defrost.
(6) Stopping the product midway will retain the temperature setting which was effective at the time of
stoppage and continues to count the time.
(7) Changing the time setting midway will clear the temperature setting, time, and all other settings
and make a fresh start.
(8) Canceling with the cancel key and sleep key will clear everything.
(9) The temperature setting is not shifted with time elapsed.
External
temperature
Heating, sleep
Set a time
As-desired "powerful" operation
Remote control
"POWERFUL" lit
Temperature
setting
Notes:
(1) Pressing the as-desired button will increase the setting by PWSFTW.
(2) The compressor's maximum speed during powerful operation will be canceled 60 minutes later.
The lower limit running speed is increased for 120 minutes after the product is set to powerful
operation, or 120 minutes after the thermometer is reset, or 120 minutes after the reset of the
defrost.
(3) The thermometer is forcibly turned on for 20 minutes after the powerful operation is reset.
(4) Defrost is inhibited for 20 minutes after the start of the powerful operation.
(5) Pressing the as-desired button during powerful operation will cancel the powerful operation.
(6) If the sleep timer is set during powerful operation, the powerful operation will be canceled.
(7) If the fan speed of the remote control is set to AUTO or "HI," the compressor's
maximum speed during powerful operation will be set to WMAX2 and the lower limit speed
WKYMIN_PW.
(8) If the fan speed of the remote control is set to "MED", the compressor's maximum
speed during powerful operation will be WJKMAX_PW and the lower limit speed WJKMIN_PW.
(9) If the fan speed of the remote control is set to "LOW", the compressor's maximum
speed during powerful operation will be set to WBEMAX_PW. The lower limit speed is
WBEMIN_PW.
(10) If the fan speed of the remote control is set to "SILENT", the compressor's maximum speed
during powerful operation will be WSZMAX_PW. The lower limit speed is WSZMIN_PW.
Note:
1. For the constants expressed in uppercase alphabet letters in the figure,
see the data in PWRITE-ZU.
– 107 –