Section 3-3-3: Heat Shields
Installing a Wall Mounted RHS8 Heat shield
The RHS8 Heat shield CANNOT be used WITHIN 36" horizontal
or 60" vertically of the fireplace, (see figure 14a). For applications
within these dimensions the RHS101 Heat Shield MUST be used.
To install the RHS8, frame an opening in combustible construction,
Figure 14 below. Slide the Heat shield in place over the vent pipe
which attaches to the fireplace. After the fireplace and vent pipe has
been installed, clearances should match the dimensions in Figure 14.
1" Min.
Figure 14. RHS8 Installation. (Install by sliding over vent pipe where it
passes through the combustible construction).
Figure 14a. RHS8 Installation. (Minimum requirements).
Page 16
Installation
1" Min. Both sides Typical
RHS8 Heat Shield
Combustible Framing
36" Min
RHS8 Heat
Shield
Termination
60" Min.
Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used where the RHS8
Termination (Figure 14 and 14a) CANNOT be used. Use the
RHS101 where any of the dimensions are within the parameters
shown, figure 14a. To install the RHS101, Slide the Inner Section
over the vent pipe that will connect to the fireplace. Then fasten the
vent pipe to the back of the fireplace with a minimum of three sheet
metal screws. From the outside slide the RHS101 outer section on
see Figure 15. To complete the installation fasten the Heat Shield
Outer Section & Termination frame to the structure Figure 15a.
RHS101 Heat Shield
Outer Section
Termination
Figure 15. RHS101 Installation. (Install by sliding Outer Section over
vent pipe where it passes through the combustible construction.
Outer Section
RHS101 Heat Shield
Termination
Figure 15a. Heat Shield. After sliding the outer section in place.
3/8" Min.
Figure 15b. RHS101 Installation.
Drywall / sheetrock
RHS101 Heat Shield, inner Section
Vent pipe, from fireplace
Combustible
framing
Drywall / sheetrock
RHS101 Heat Shield, inner Section
3/8" Min. Both sides Typical
Inner Shield 9 3/8"
Outer Shield 10 1/4"
Combustible Framing
XG0810 - 070714