Converter B2F020 - Siemens Cerberus MN7002 Manual

Siemens cerberus mn7002 power supply manual
Table of Contents

Advertisement

2

Converter B2F020

115/230V
AC
29.6V
DC
Fire & Security Products
Siemens Building Technologies Group
Fixing point for
mains cable
Key data B2F020
Mains voltage
Power consumption
Mains fuse
Output current
Output voltage
Residual ripple
Quiescent current on battery
operation
Temperature fuse
Cooling
Temperature range
Standard
Dimensions
Wire range
Connections of B2F020
B2F020
Input voltage
(115V
) 230V
/ 50...60Hz
AC
AC
max. 220VA
Output voltage
29.6V
/ max. 6A
DC
115V
AC
230V
AC
±15% 50...60Hz
115 / 230V
AC
40...220VA
3.15A slow-blow (can only be changed at factory)
up to 6A continuous
+2%
29.6V
DC
max. 300mVpp
0mA
automatic switch-off at >90°C
no special cooling required
0...+55°C
prEN54-4
120 (100) x 42 x 204mm
2
max. 4mm
L
N
E
Opt
Sd
– S
Jumpers inserted ex factory
(essential, do not remove)
+ S
+
11
+
10
Disconnect mains
voltage before open-
ing converter cover!
Mains voltage change-over:
1. Remove converter cover.
2. Change cable connect position.
Default = 230V
AC
≤10A
Mains
E3C021
3
e1493d
04.2002

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents