Pipe Insulation - Panasonic CS-E10JD3EA Service Manual

Air conditioner
Hide thumbs Also See for CS-E10JD3EA:
Table of Contents

Advertisement

(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × 1.5 mm
cord, type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Cable connection to the power supply (230 - 240V, 50Hz) through knife switch (Disconnecting means).
• Connect the approved polychloroprene sheathed power supply cable (3 x 1.5 mm
cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).
Note: Knife switch (Disconnecting means) should have minimum 3.5 mm contact gap.
- Secure the cable onto the control board with the holder (clamper).

11.2.6. PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E
FOAM with thickness 8 mm or above.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
• If a drain elbow is used, the unit should be placed on a stand
which is taller than 3 cm.
• If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan will
not rotate.
2
), type designation 245 IEC 57 or heavier
43
2
flexible

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents