Electrical Connections - Jacuzzi FUZION BATH SERIES 7260 Installation & Operation Instructions

Jacuzzi whirlpool user manual
Hide thumbs Also See for FUZION BATH SERIES 7260:
Table of Contents

Advertisement

Electrical Connections

Separate circuits for all (except the Fuzion 7260 Dual motor) tubs, each must be protected by a Ground Fault
Circuit Interrupter (GFCI), are required for the pump/motor and the RapidHeat
tubs require two (2) separate circuits, each must be protected by a Ground Fault Circuit Interrupter (GFCI), for each
pump/motor and RapidHeat
Refer to the electrical specification for each model on pages 6 - 7. Install duplex outlets to the studwall underneath
the bathtub, at least 4 inches (10,2 cm) above the floor or in accordance with local building or electrical codes. Duplex
outlets are not provided. Because these units are manufactured with an electronic control panel no remote switch or
timer is necessary.
Tubs with electronic control panels combine the electrical requirements of the pump/motor and electronic controls
into a control box. For these units the power supply cord from the pump/motor runs to the control box. The power
supply cord from the control box should be connected to the correctly rated amperage GFCI circuit.
Before installing electrical connections, inspect the pump/motor and heater nameplates and confirm you have 120
VAC, 20 AMP and 15 AMP or 230 VAC, 20 AMP service requirements. The GFCI circuits must match these require-
ments. Care must be taken:
FOR 120 VAC units
Connect the 120 VAC, 20 AMP pump/motor or control box power cord ONLY to the 120 VAC, 20 AMP GFCI circuit
Connect the 120 VAC, 15 AMP heater power cord ONLY to the 120 VAC, 15 AMP GFCI circuit.
FOR 230 VAC units
Connect one 230 VAC, 20 AMP control box power cord controlling one pump/motor and heater set ONLY to one
230 VAC, 20 AMP GFCI circuit.
Connect the second 230 VAC, 20 AMP control box power cord controlling the other pump/motor and heater set
ONLY to the other 230 VAC, 20 AMP GFCI circuit.
Do NOT switch power cords and GFCI circuits.
With a #8 solid copper wire (not provided), bond the heater to the house electrical panel or approved local bond. A
bonding lug is provided on the heater. With another #8 solid copper wire (not provided), bond the pump/motor to the
house electrical panel or approved local bond. A bonding lug is provided on the pump/motor.
At initial start-up and before each use thereafter with power ON, push the GFCI test button on each circuit. The
reset button should pop out. Push this button in to reset. If the interrupter fails to operate in this manner, there is a
ground current flowing or a device malfunction, indicating the possibility of electrical shock. Turn OFF power and do
not use the bath until the source of the problem has been identified and corrected.
DANGER: RISK OF ELECTRIC SHOCK. Connect only to a circuit protected by a Ground Fault Circuit Inter-
rupter (GFCI).
CAUTION: Operating the motor/pump without enough water in the bath can cause leaking and permanent
damage to the pump. Before power is applied to the installation, make sure the switch is in the OFF position
to avoid pump damage.
ELECTRICAL CONNECTION 120 VAC ONLY
15 AMP, 3 PRONG PLUG
(Heater)
20 AMP, 3 PRONG PLUG
(Pump/Motor)
TM
HEATER
Jacuzzi Whirlpool Bath DE99000A
INSTALLATION INSTRUCTIONS
TM
Heater combination.
DUPLEX
RECEPT.*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
ELECTRICAL
CODES
* INSTALL SEPERATE
GFCI PROTECTED CIRCUITS,
DUPLEX RECEPTS NOT PROVIDED
3/06
TM
Heater. The Fuzion 7260 Dual motor
ELECTRICAL CONNECTION - HEATER AND PUMP/MOTOR 230V
TM
HEATER
16
230V GFCI
PROTECTED
CIRCUIT*
4" MIN.
OR IN
ACCORDANCE
WITH LOCAL
BUILDING OR
ELECTRICAL
CODES
SUPPLIED POWER CORD
FROM JUNCTION BOX TO
GFCI PROTECTED
CIRCUIT
*(NOT PROVIDED)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fuzion seriesFuzion 7236Fuzion 6666

Table of Contents