ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
Model
precharged
MUZ-A09YV -
E1
MUZ-A09YVH -
E1
MUZ-A12YV -
E1
MUZ-A12YVH -
E1
8

PERFORMANCE CURVES

MUZ-A09YV -
E1
MUZ-A09YVH -
E1
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
(4) Total input:
(5) Indoor intake air dry-bulb temperature :
(6) Outdoor intake air wet-bulb temperature :
(7) Total input :
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1.
Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2.
Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3.
Check that the air filter is cleaned.
4.
Open windows and doors of room.
5.
Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6.
When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7.
10 minutes later, measure temperature again and check that the temperature does not change.
5m
6m
800
0
0
900
0
0
MUZ-A12YV -
E1
MUZ-A12YVH -
E1
www.ilmalämpöpumput.com
Refrigerant piping length (one way)
7m
9m
10m
8m
0
90
120
150
0
120
150
90
Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)
°C WB
}
°C WB
Cooling
°C DB
W
°C DB
}
°C WB

Heating

W
12
11m
12m
13m
14m
180
210
240
270
180
210
240
270
15m
20m
300
450
300
450