Mitsubishi Electric MUZ-A09YV-E1 Service Manual page 36

Split-type, heat pump air conditioners
Table of Contents

Advertisement

Mitsubishi Electric ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy
OPERATING PROCEDURE
4. Removing the defrost thermistor and discharge tem-
perature thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the indoor/outdoor connecting wire and remove
the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its
holder. (Photo 5)
Photo 5
Photo 6
36
www.ilmalämpöpumput.com
PHOTOS
R.V. coil
Discharge temperature thermistor
Defrost
thermistor