1. Troubleshooting check table
NOTE 1. The location of LED is illustrated at the right figure. Refer to page 32.
2. LED lights up during normal operation.
Symptom
No.
LED indication
1-time flash every
Outdoor unit
2.5 seconds
1
does not
operate
NOTE:
For abnormality
2
location, refer to
'Indoor
troubleshooting
check table'.
3
Refer to service
manual OB327.
4
2-time flash
'Outdoor unit
2.5 seconds OFF
5
stops and
restarts 3
minutes later'
3-time flash
is repeated
2.5 seconds OFF
6
4-time flash
2.5 seconds OFF
7
5-time flash
2.5 seconds OFF
8
8-time flash
9
2.5 seconds OFF
1-time flash
Outdoor unit
2.5 seconds OFF
10
operates (at
low
frequency)
3-time flash
2.5 seconds OFF
11
4-time flash
2.5 seconds OFF
12
5-time flash
Outdoor unit
operates
2.5 seconds OFF
13
7-time flash
2.5 seconds OFF
14
8-time flash
2.5 seconds OFF
15
9-time flash
2.5 seconds OFF
16
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is "2".
ON
OFF
Abnormal point/ Condition
When compressor has stopped by overcurrent protection within
Outdoor power
1 minute 3 times in a row after compressor start-up, unit stops.
system
Outdoor
When discharge temperature thermistor, fin temperature
thermistor or defrost thermistor shorts or opens during
thermistors
compressor running, compressor stops and restarts 3 minutes
later.
Outdoor control
When nonvolatile memory data cannot be read properly,
system
compressor stops and restarts 3 minutes later.
When the bus-bar voltage of inverter cannot be detected
Bus-bar voltage
normally.
Overcurrent
When 12A(MUZ-A09YV, MUZ-A09YVH)/ 20A(MUZ-A12YV,
protection
MUZ-A12YVH) current flows into power transistor module,
compressor stops and restarts 3 minutes later.
Discharge
When discharge temperature thermistor exceeds 116:,
temperature
compressor stops. Compressor can restart if discharge
overheat
temperature thermistor reads 100: or less 3 minutes later.
protection
Fin temperature
When temperature at heat sink exceeds 83: or temperature of
thermistor overheat
inverter P.C. board exceeds 79:, compressor stops and
protection
restarts 3 minutes later.
When indoor coil thermistor exceeds 70:.
High pressure
When the defrost thermistor exceeds 70: in COOL mode.
protection
Compressor
When the waveform of compressor current is distorted.
sinusoidal current
Frequency drop by
When current from power outlet exceeds 7A(MUZ-A09YV,
current protection
MUZ-A09YVH)/ 9A(MUZ-A12YV, MUZ-A12YVH), compressor
frequency lowers.
Frequency drop by
When indoor coil thermistor exceeds 55: in HEAT mode,
high pressure
compressor frequency lowers.
protection
Frequency drop by
When indoor coil thermistor reads 6: or less in COOL mode,
defrosting in COOL
compressor frequency lowers.
mode
Frequency drop by
When discharge temperature thermistor exceeds 110:,
discharge
compressor frequency lowers.
temperature
protection
When ambient temperature thermistor shorts or opens during
Outdoor
compressor running.
thermistors
Low discharge
When discharge temperature has been 40: or less for 20
temperature
minutes.
protection
When the overcurrent flows into IGBT(Insulated Gate Bipolar
PAM protection
transistor : TR821) or when the bus-bar voltage reaches 300V
or more, PAM stops and restarts.
PAM:
Pulse
Amplitude
Modulation
When the connector of compressor is disconnected, inverter
Inverter check
check mode starts.
mode
2.5-second OFF
www.ilmalämpöpumput.com
Detection method
0.5-second ON
2.5-second OFF
24
<Inverter P.C. board>
LED
Flashing
Checkpoint
· Check stop valve.
· Reconnect connectors.
· Refer to A "How to check inverter/
compressor" on page 26.
· Refer to G "Check of outdoor
thermistors" on page 28.
Replace inverter P.C. board after
check of A "How to check inverter/
compressor" on page 26 and G
"Check of outdoor thermistors" on
page 28.
Refer to A "How to check inverter/
compressor" on page 26.
· Check stop valve.
· Reconnect connectors.
· Refer to A "How to check inverter/
compressor" on page 26.
· Check refrigerant circuit and
refrigerant amount.
· Refer to G "Check of outdoor
thermistors" on page 28.
· Refer to L "Check of LEV" on page
30.
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to I "Check of outdoor fan
motor" on page 29.
· Check refrigerant circuit and
refrigerant amount.
· Check stop valve.
· Check stop valve.
· Reconnect connector.
· Refer to A "How to check inverter/
compressor" on page 26.
The unit is normal, but check the
following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to G "Check of outdoor
thermistors" on page 28.
· Refer to L "Check of LEV" on
page 30.
· Check refrigerant circuit and
refrigerant amount.
This is not malfunction.
PAM protection will be activated in
the following cases;
1Instantaneous power voltage drop
(Short time power failure)
2When the power supply voltage is
high.
Check if the connector is correctly
connected.
Refer to A "How to check inverter/
compressor" on page 26.
0.5-second ON