9-10. Operational frequency control of outdoor unit
1. Outline
The operational frequency is decided by following the procedures below:
First, set the target operational frequency based on the difference between the room temperature and the set temperature.
Second, regulate the target operational frequency by discharge temperature protection, high pressure protection, electric
current protection and overload protection and also by the maximum/minimum frequency.
(1) maximum/ minimum frequency in each operation mode.
COOL (indoor fan speed : Hi)
Model
Minimum
frequency
MSZ-A09RV
15
MSZ-A12RV
15
w The maximum frequency in COOL mode is limited according to operation hours, as shown below.
Maximum
frequency
frequency
1Hr
(2) Frequency change speed
During increasing frequency
Operational frequency
10Hz to 14Hz
15Hz to 79Hz
80Hz to 150Hz
During decreasing frequency
Operational frequency
10Hz to 42Hz
43Hz to 150Hz
Rating
Maximum
frequency
frequency
53
80
82
88
Rating or under-rating frequency
Time
MUZ-A09RV-
MUZ-A09RV-
HEAT
Minimum
Rating
frequency
frequency
16
67
16
98
MUZ-A12RV-
E1
E1
0.5 sec./Hz
5 sec./Hz
0.5 sec./Hz
MUZ-A12RV-
E1
E1
1 sec./Hz
0.5 sec./Hz
33
Maximum
DRY
frequency
98
22/27
115
22/27