8.15 Automatic panel function

1)
The automatic panel is forced to turn to the closing direction at an angle of 50°when the unit is getting through the
power, and this action is not affected by any signal from remote controller.
2)
When the unit is turned on, the panel is opened automatically at an angle of 50°, then the horizontal louver will be
opened.
3)
When the unit is turned off, the panel is closed automatically at an angle of 50°, then the horizontal louver will be
closed.
4)
If the panel needs moving when the horizontal louver is in action, the unit will stop the horizontal louver and then carry
out the action of the panel. After ending the action of the panel, the horizontal louver will continue its action.

8.16 Ionizer (Clean Air) function

1)
Clean Air function is available only when the aircon is on, and it's controlled through remote controller..
2)
After the Aircon being turned on, the Clean Air function is switched on when the aircon receives FRESH CODE at
first time, and ionizer is switched off when the aircon receives the CODE again. It's a circle.
3)
After starting the Clean Air function, the ionizer can work only when the indoor fan motor is running. If the indoor fan
motor is off, the ionizer also stops working, even though the Clean Air function is available.
4)
Switching the running mode will not stop the ionizer. When turning off the aircon, the ionizer is also turned off.

8.17 Self-clean function

1) Self-clean function is chosen through wire jumper J2 in indoor PCB, it's available when the unit has detected that J2
is on after getting through the power.
2) Self-Clean function is available only at cooling (including auto-cooling and turbo) and drying mode, when the user
press down the button "Self-Clean" on remote controller, the "Self-Clean" icon on LCD screen of indoor unit will keep
bright. After running for 13 minutes in low fan mode, the unit turns into low heating mode(anti-cold wind function is not
valid), when the unit keeps low heating mode for 1 min or evaporator high temp protection occur, it stops and turns into
low fan mode and keeps running for 2 minutes, then quits from Self-Clean function and turns off.
3) When setting the Self-Clean function, the unit has been in Timer or Turbo function, the Timer or Turbo function will
be cancelled and then execute Self-Clean function.
4) When the unit is running Self-Clean function, all functions are not available except swing/air direction/clean air/LED
display, and only receiving "Self-Clean" code again or "turn off" code, the unit can quit from the function.
5) When the unit is running Self-Clean function, all protection functions are valid.

8.18 Follow me function

1)
Follow me function is chosen through wire jumper J1 in indoor PCB, it's available when the unit has detected that J1
is on after getting through the power.
2)
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the
buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal
which sent from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with follow
me function, the PCB will control the unit according to the temperature from follow me signal, and the temperature
collection function of room temperature sensor will be shielded, but the error detective function of room temperature
sensor will be still valid.