Haier HC18D1VAR Service Manual page 17

Central air conditioning
Table of Contents

Advertisement

Refrigerant Line Sizing
Unit Size
(Ton)
Suction
1.5
3/4
2.0
3/4
2.5
3/4
3/4
3.0
3.5
7/8
4.0
7/8
5.0
7/8
The factory charge is sufficient for 25 feet of standard liquid line. For longer or shorter liquid line
lengths, adjust the charge as follows:
1/4" Line
+/- 0.3 oz. Per foot
5/16" Line
+/- 0.4 oz. Per foot
3/8" Line
+/- 0.6 oz. Per foot
1/2" Line
+/- 1.2 oz. Per foot.
Vertical Separation between Indoor and Outdoor Units
Maximum allowable vertical separations between indoor and outdoor units are illustrated in Fig.
7-2-C and Fig. 7-2-B. It's 70' when the indoor unit is below the outdoor unit (Fig.7-3-B), and 50'
when the indoor unit is above the outdoor unit (Fig. 7-2-B) .C
To ensure good oil return to the compressor when the indoor unit is below the outdoor unit,
suction line oil trap should be used as illustrated in Fig. 7-2-B.
Interconnecting piping
! CAUTION -
Use caution when removing the service valves caps from the suction and liquid line
there is pressure present. A fitting is on the liquid line to remove pressure.
fittings, as
! CAUTION -
Condensing units ship from the factory with an operating refrigerant charge. Heat pump
unit liquid and suction valves are closed to contain the charge within the unit. Do not force the valve
stem against the retaining ring. If the valve stem is backed out past the retaining ring, system pressure
could force the valve stem out of the valve body and possibly cause personal injury.
Instructions on the interconnecting piping and valve opening procedure are listed below:
1.Tubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the
tubing to prevent contamination from entering the system.
2.Make sure that both refrigerant shutoff valves at the outdoor unit are closed.
3.Push the tubing into the fitting until it stops. This prevents flux from getting into the system.
4.Remove the cap and Schrader valve core from the service port to protect the valve seals.
5.Wrap a wet rag around the valve stub before brazing.
6. Braze the joints of interconnecting piping. purge piping with dry nitrogen through the shutoff valve port
while brazing.
7.After brazing quench with a wet rag to cool the joint. Reinstall the Schrader core in the valve, if
removed for brazing.
17
Central Air Conditioner
Refrigerant Line Length (Ft)
0 – 24
Line Outside Diameter (In)
Liquid
Suction
3/8
3/8
3/8
3/8
11/8
3/8
3/8
3/8
Table 7-1
Model: Cooling Only, 13SEER units
25 – 49
Liquid
3/8
3/4
3/4
3/8
3/4
3/8
3/4
3/8
3/8
11/8
3/8
11/8
3/8
50 – 74
Suction
Liquid
7/8
1/2
7/8
1/2
7/8
1/2
1/2
7/8
11/8
1/2
11/8
1/2
11/8
1/2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hc24d1varHc36d1varHc30d1varHc42d1varHc48d1varHc60d1var