Installer Setting -Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Pressure selection
01
02
03
04
16 Wide Wired Remote Controller
V-H
F-H
V-L
F-L
1
Press
button for 4 seconds
to enter the installer setting
mode until timer segment
display "01:01".
2
Repeat pressing
Function code 06.
Function Code
3
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
4
Press
button to save or
release.
5
Press
button to exit or
system will automatically exit
after 25 seconds without any
input.
Function
Zone state
Variable
Fixed
Variable
Fixed
button to select
Pressure
ESP standard value
High
High
Low
Low

Hide quick links: