A list of available operating lines appears on screen.
3. Select Hours / minutes and press the OK button.
The setting for hours starts blinking on screen.
4. Set current time in hours and press the OK button.
The setting for minutes starts blinking on screen.
5. Set current time in minutes and press the OK button.
6. Select Month / day and press the OK button.
The setting for months begins blinking on screen.
7. Set current month and press the OK button.
The setting for days starts blinking on screen.
8. Set current day and press the OK button.
9. Select Year and press the OK button.
The setting for years starts blinking on screen.
10. Set current year and press the OK button.

2.7. Configuring heating curve

1. Press the OK button to access the menu system.
2. Select the correct heating circuit settings menu and press the OK button.
Depending on the heating circuit that you want to configure, select Heating
circuit 1 or Heating circuit 2.
3. Select Comfort setpoint and press the OK button.
4. Set the correct comfort setpoint value and press the OK button. This value is used
as the basis for the heat curve calculation.
5. Select Heating curve slope and press the OK button.
6. Set the correct heating curve slope and press the OK button.
Depending on the heating system type of the building, the recommended values
are:
Approximately 0.4 for houses with floor heating
Approximately 0.6 for houses with radiator heating
It is not recommended to use bigger value than 1.0.
The following figure displays different heating curves all of which are based
on an indoor temperature of 20 °C. The horizontal axis shows the ambient
temperature outdoors and the vertical axis shows the water temperature as it
enters the heating circuit.
20 15
10
HC ver. 2
7. Select Flow temp setpoint min and press the OK button.
8. Set the correct value and press the OK button.
9. Select Flow temp setpoint max and press the OK button.
10. Set the correct value and press the OK button.
12 (24)
5
-10 -15 -20 -25 -30 -35 -40
0
-5
°C
70
1
60
0.8
50
0.6
°C
40
0.4
0.2
30
0
20
10
GT02 1408 EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sh 7Gt 7Gt 9Gt 11Gt 13Gt 16 ... Show all