Mitsubishi Electric PRH-P8MYA Technical & Service Manual page 52

Air-cooled rooftop packaged air conditioners
Hide thumbs Also See for PRH-P8MYA:
Table of Contents

Advertisement

SW2 setting
Display contents
Outdoor-side unit set
information 1
1 2 3 4 5 6
ON
OFF
Outdoor-side unit set
information 2
1 2 3 4 5 6
ON
OFF
Indoor-side unit piping
temperature (TH5)
Indoor 1
1 2 3 4 5 6
–40 - 90
ON
OFF
Indoor-side unit
intake temperature
(TH4)
1 2 3 4 5 6
ON
8 - 39.5
OFF
Indoor
set temperature
1 2 3 4 5 6
17 - 30
ON
OFF
Description of display
Outdoor-side unit capacity is displayed as function code.
Model name
function code
PRH-P8MYA
20
PRH-P10MYA
25
PRH-P16MYA
20 + 20
PRH-P20MYA
25 + 25
Outdoor-side unit set information 1
3-phase power source detection Do
Cooling only switching
Cooling only
Night mode
Night mode
12 °C continuous 2 minutes (2) 8 °C continuous 2 minutes (0)
Defrosting end time
Defrosting prohibit time
Fixed
Set information display values are added and displayed at each position.
–40 - 90
(When 0 °C or lower, "–"and temperature are displayed
alternately.)
When there are no indoor-side unit, "00" is displayed.
8 - 39.5
When there are no indoor-side unit, "00" is displayed.
17 - 30
When there are no indoor-side unit, "00" is displayed.
- 49 -
Function setting (display valves)
(1) Do not
(0)
(2) H/P
(0)
(1) Normal mode
(0)
(4) Training
(0)
Unit
Code display
Code display
°C
°C
°C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prh-p10myaPrh-p16myaPrh-p20mya

Table of Contents