SW2 setting
Display contents
Indoor-side
control status
1 2 3 4 5 6
ON
OFF
Outdoor-side unit
condenser/evaporater
temperature (TH3)
1 2 3 4 5 6
ON
–39 - 88
OFF
Outdoor-side
control status
1 2 3 4 5 6
ON
OFF
Discharge super heat
SHd
0 - 216
Cooling: Outdoor-side
1 2 3 4 5 6
ON
OFF
Heating: Outdoor-side
Sub cool Sc
0 - 130
Cooling: Outdoor-side
1 2 3 4 5 6
ON
OFF
Heating: Indoor-side
Target sub cool step N
1 2 3 4 5 6
ON
1 - 5
OFF
Control mode display system
–39 - 88
(When 0 °C or lower, "–"and temperature are displayed
alternately.)
<Example> When –10,
Control mode display system
0 - 216
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 150,
TH2
– Outdoor-side
TH3
TH2
– Indoor-side
TH6
0 - 130
TH3
(When 100 or higher, 100s digit and 10s and units digits
– Outdoor-side
are displayed alternately.)
TH1
<Example> When 100,
TH6
– Indoor-side
TH5
1 - 5
Description of display
Display
0
1
2
Indoor-side
3
4
5
6
7
every other second
←→ –10
Display
0
1
2
Outdoor-side
3
4
5
6
7
every other second
←→ 50
1
every other second
←→ 00
1
- 50 -
Unit
Control mode
Indoor-side
Ordinary
Hot adjustment
Defrosting
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
°C
Control mode
Outdoor-side
Ordinary
Hot adjustment
Defrosting
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
°C
°C